140AIO33000C
Schneider Electric 140AIO33000C
MPN140AIO33000C
Obsolete
intrinsically safe analog output module - Modicon Quantum - 8 O
$3,034.58Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jun 2026
Specifications
| Parameter | Value |
|---|---|
| Fault type | Open circuit 4...20 mA |
| Protection type | Internal fuse |
| Range of product | Modicon Quantum automation platform |
| Product or component type | Intrinsically safe analog output module |
| Bus current requirement | 2.5 A |
| Power dissipation in | 12.5 W |
| Relative humidity | 95 % without condensation |
| Operating altitude | <= 16404.2 ft (5000 m) |
| Standards | UL 508 EN 50281-1-1 EN 50020 EN 50014 CSA C22.2 No 142 EN 50039 Directive ATEX 94/9/EC EN 50284 |
| Marking | CE II1 G/D-EEx ia IIC |
| Category | 18155-QUANTUM I/O & POWER SUPPLIES |
| Dust zone | Outside zone |
All specifications+18 ▾
| Parameter | Value |
|---|---|
| Linearity | +/- 1 LSB |
| Update time | 4 ms |
| Setting time | 1 ms to +/- 0.1 % of the final value |
| Module format | Standard |
| Product destination | In conjunction with products for zone 20, 21 or 22 |
| Protective treatment | Conformal coating Humiseal 1A33 |
| Software designation | Unity Pro Concept V2.2 and above ProWORX |
| Analogue output range | 0...20 mA 0 to 20000 points 0...25 mA 0 to 25000 points 4...20 mA 15 bits, 0 to 16000 points 4...20 mA 15 bits, 0 to 4095 points |
| Hot swapping fallback | Not allowed per intrinsic safety standards |
| Analogue output number | 8 |
| Absolute accuracy error | +/- 0.2 % of full scale 77 °F (25 °C) |
| Maximum loop resistance | 500 Ohm |
| Isolation between channels and bus | 1780 Vrms 60 s AC |
| Ambient air temperature for storage | -40...185 °F (-40...85 °C) |
| Resistance to electromagnetic fields | 9.1 V/m (10 V/m) 80...2000 MHz IEC 801-3 |
| Ambient air temperature for operation | 32...140 °F (0...60 °C) |
| Resistance to electrostatic discharge | 4 kV contact IEC 801-2 8 kV on air IEC 801-2 |
| Accuracy drift according to temperature | 40 ppm/°C |
MPN
140AIO33000C