Skip to main content
Schneider Electric 140CRA93200

140CRA93200 Modicon Quantum RIO Drop Adapter, 2 Connector

MPN140CRA93200
End of Life

Modicon Quantum automation platform, RIO drop adaptor module, 140CRA93200, two coaxial connectors, 500 V DC isolation, UL 508 listed.

$556.00 – $1,016.36Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

140CRA93200 key specifications
ParameterValue
Type of cable75 Ohm coaxial
Range of productModicon Quantum automation platform
Product or component typeRIO drop adaptor module
Isolation voltage500 V DC coaxial center and ground
Bus current requirement750 mA 2 channels
Power dissipation in3.8 W 2 channels
Electrical connection2 female connectors F, elbowed with redundant cable
Relative humidity95 % without condensation
Operating altitude<= 16404.2 ft (5000 m)
StandardsUL 508 CUL CSA C22.2 No 142
CategoryUS1PC2118155
Dynamic range35 dB

All specifications

140CRA93200 additional specifications
ParameterValue
Module formatStandard
Transmission rate1544 Mbit/s
Diagnostics startupPower up and runtime RAM address/data Executive checksum
Ambient air temperature for storage-40...185 °F (-40...85 °C)
Resistance to electromagnetic fields9.1 V/m (10 V/m) 80...1000 MHz IEC 801-3
Ambient air temperature for operation32...140 °F (0...60 °C)
Resistance to electrostatic discharge4 kV contact IEC 801-2 8 kV on air IEC 801-2

Product details

The 140CRA93200 is a RIO drop adaptor module for the Modicon Quantum automation platform, configured for Ethernet/IP with two female coaxial connectors for redundant cable runs. The module operates over a 0 to 60 °C ambient range with 95% non-condensing humidity, and is rated for altitudes up to 5000 m.

The coaxial interface is isolated at 500 V DC between center conductor and ground, and the module draws 750 mA from the Quantum backplane, dissipating 3.8 W across two channels. Diagnostics include power-up and runtime RAM/executive checksum verification. The module is listed under UL 508, CUL, and CSA C22.2 No 142.

Frequently asked questions

What standards does the 140CRA93200 comply with?

The module is listed under UL 508, CUL, and CSA C22.2 No 142.

What is the operating temperature range of the 140CRA93200?

The operating ambient temperature range is 32 to 140 °F (0 to 60 °C).

What is the bus current draw of the 140CRA93200?

It draws 750 mA from the Quantum backplane, shared across two channels.

MPN
140CRA93200