Specifications

140DRA84000 key specifications
ParameterValue
Range of productModicon Quantum automation platform
Product or component typeRelay discrete output module
Contacts type and composition1 NO
Discrete output voltage20...250 V AC 30...150 V DC 5...30 V DC
Surge current10 A 10 ms capacitive
Maximum load current1 A 250/30 V AC/DC 1/8 hp cos phi = 0.4 1 A 250/30 V AC/DC tungsten 2 A 250/30 V AC/DC resistive 140 °F (60 °C) 300 mA 30...50 V DC resistive
Bus current requirement1100 mA
Power dissipation5.5 W + (0.5 x the number of points on)
Contact formForm A
Maximum response time on input open10 ms at state 0 to state 1 20 ms at state 1 to state 0
Relative humidity95 % without condensation
Operating altitude<= 16404.2 ft (5000 m)

All specifications

140DRA84000 additional specifications
ParameterValue
Electrical durability100000 cycles 100 mA 30...150 V DC L/R = 10 ms 100000 cycles 2 A 30 V DC resistive 100000 cycles 30...150 V DC interposing relay 100000 cycles 300 mA 30...150 V DC resistive 200000 cycles 2 A 250 V AC resistive 50000 cycles 500 mA 30...150 V DC resistive
Mechanical durability10000000 cycles
StandardsUL 508 CSA C22.2 No 142
MarkingCE
CategoryUS1PC2118155
Minimum load50 mA 20...250 V AC 50 mA 5...30 V DC
Module formatStandard
Local signalling1 LED (green) for bus communication is present (Active) 1 LED (red) for external fault detected (F) 16 LEDs (green) for input status
Addressing requirement1 output word
Discrete output number16
Switching capacity in500 VA resistive
Isolation between channels1780 Vrms AC for 1 minute
Output overvoltage protectionInternal by varistor, 275 V
Isolation between channels and bus1780 Vrms AC for 1 minute 2500 V DC for 1 minute
Ambient air temperature for storage-40...185 °F (-40...85 °C)
Resistance to electromagnetic fields9.1 V/m (10 V/m) 80...2000 MHz IEC 801-3
Ambient air temperature for operation32...140 °F (0...60 °C)
Resistance to electrostatic discharge4 kV contact IEC 801-2 8 kV on air IEC 801-2