Its 50 kA interrupting capacity at 400/690 VAC means it can safely clear high-fault currents on industrial supply lines without upstream device coordination issues — a key spec for panel builders needing selectivity headroom.
What Curve K means for the buyer
Trip Curve K provides a magnetic trip threshold of 8 to 12 times rated current (In), placing it between Curve C (5–10× In) and Curve D (10–20× In).
The 3-pole footprint occupies three module widths (17.5 mm per pole). Rated operational voltage is 400/690 VAC, 375 VDC, at 50/60 Hz. The thermal-magnetic trip mechanism requires no external power supply for protection — it's self-powered from the line side.