Miniature circuit breaker (MCB), Acti9 NG125a, 4P, 80A, C curve, 16kA (IEC/EN 60947-2)

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

18607 — Identification
ParameterValue
Product / component typeMiniature circuit-breaker
Product nameActi9 NG125
Product rangeActi9
Device applicationDistribution
18607 — Electrical
ParameterValue
Network type (AC/DC)AC DC
Rated current [In]80 A at 40 °C
Rated operational voltage [Ue]380...415 V AC 50/60 Hz 500 V AC 50/60 Hz <= 500 V DC
Rated insulation voltage [Ui]690 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage [Uimp]8 kV conforming to EN/IEC 60947-2
Network frequency50/60 Hz
Poles description4P
Magnetic tripping limit8 x In
18607 — Protection & Performance
ParameterValue
Breaking capacity16 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 8 kA Icu at 500 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at <= 500 V DC conforming to EN/IEC 60947-2
Rated service breaking capacity [Ics]12 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 6 kA 75 % conforming to EN/IEC 60947-2 - 500 V AC 50/60 Hz 20 kA 100 % conforming to EN/IEC 60947-2 - 500 V DC
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to IEC 60947-2
Utilisation categoryCategory A conforming to IEC 60947-2
Mechanical durability20000 cycles
Electrical durability5000 cycles
Local signallingTrip indicator ON/OFF indication
Contact position indicatorYes
18607 — Mechanical
ParameterValue
Connections / terminalsTunnel type terminals16...70 mm² rigid Tunnel type terminals10...50 mm² flexible
Device short nameNG125a
Control typeManual tripping test Toggle
Mounting modeClip-on
Mounting support35 mm symmetrical DIN rail
Usable 9 mm pitches12
Width108 mm
Height103 mm
Depth81 mm
18607 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
IK degree of protectionIK05 conforming to EN/IEC 62262
Pollution degree3 conforming to IEC 60947-2
Operating ambient air temperature-30...70 °C
Storage ambient air temperature-40...70 °C
18607 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
18607 — Specifications
ParameterValue
Curve codeC
Number of protected poles4
MPN
18607