Skip to main content
Schneider Electric 18657 — Miniature Circuit Breakers (MCB)

Schneider Electric 18657

MPN18657
Active

NG125 - circuit breaker - NG125N - 4P - 80A - C curve

$15.78Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

18657 — Identification
ParameterValue
Product nameActi9 NG125
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution
18657 — Ratings
ParameterValue
Rated current (In)80 A at 40 °C
Poles configuration4P
Number of protected poles4
Breaking capacity20 kA Icu at 10 kA Icu at 500 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated service breaking capacity (Ics)37.5 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 18.75 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 500 V AC 50/60 Hz 20 kA 100 % conforming to EN/IEC 60947-2 - <= 500 V DC
Rated operational voltage (Ue)380...415 V AC 50/60 Hz 500 V AC 50/60 Hz 220...240 V AC 50/60 Hz 440 V AC 50/60 Hz
Rated insulation voltage (Ui)690 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to EN/IEC 60947-2
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to IEC 60947-2
Overvoltage categoryIV
18657 — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8 x In
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)5000 cycles
Mechanical durability (cycles)20000 cycles
18657 — Mechanical
ParameterValue
Mounting support35 mm symmetrical DIN rail
Mounting modeClip-on
Control typeManual tripping test Toggle
Terminal connection typeTunnel type terminals16...70 mm² rigid Tunnel type terminals10...50 mm² flexible
Terminal tightening torque6 N.m
Wire stripping length20 mm
Contact position indicatorYes
Local signalling/indicationON/OFF indication Trip indicator
Width108 mm
Height103 mm
Depth81 mm
Number of 9 mm pitches12
18657 — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...70 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1
18657 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
MPN
18657