Skip to main content
Schneider Electric 23049 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric 23049

MPN23049
Obsolete

residual current circuit breaker ID - 4 poles - 63 A - class AC 300 mA

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

23049 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)300 mA
Earth-leakage protection class / typeType AC
Earth-leakage trip time delayInstantaneous
23049 — Electrical Ratings
ParameterValue
Rated current (In)63 A
Rated operational voltage (Ue)230/400 V
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)440 V conforming to IEC 60947-3
Rated impulse withstand voltage (Uimp)6 kV conforming to IEC 60947-3
Device location in systemOutgoer
Mechanical durability (operating cycles)20000 cycles
23049 — Identification
ParameterValue
Product / component typeResidual current circuit breaker (RCCB)
Device short nameID RCCB
23049 — Mechanical
ParameterValue
Width in 9 mm modules8
Terminal connectionsTunnel type terminals35 mm² flexible Tunnel type terminals50 mm² rigid
23049 — Environmental
ParameterValue
Operating ambient temperature-5...40 °C
Storage ambient temperature-40...60 °C
Relative humidity95 % at 55 °C
Tropicalisation2
23049 — Approvals
ParameterValue
StandardsIEC 60947-1 IEC 61008 IEC 60947-3
MPN
23049