Skip to main content
Schneider Electric 24629 — 1-Pole MCB (DIN Rail)

Schneider Electric 24629

MPN24629
Obsolete

C60 - circuit breaker - C60N - 1P - 6A - D curve

$24.50Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

24629 — Identification
ParameterValue
Product nameC60
Product / component typeMiniature circuit-breaker
Product rangeMulti9
Device short nameC60N
Poles description1P
Number of protected poles1
Device applicationDistribution
24629 — Electrical & Protection
ParameterValue
Rated current (In)6 A at 40 °C
Rated operational voltage (Ue)230...240 V AC 50/60 Hz 400...415 V AC 50/60 Hz 130 V AC 50/60 Hz 230/400 V AC 50/60 Hz
Tripping curve codeD
Magnetic tripping limit10...14 x In
Breaking capacity (Icu / AIR)20 kA Icu at 130 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 230...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 3 kA Icu at 400...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 230/400 V AC 50/60 Hz conforming to EN 60898 15 kA Icu at 60 V DC 1P conforming to EN/IEC 60947-2
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
24629 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid
Mounting support35 mm symmetrical DIN rail
Mounting modeClip-on
Width18 mm
Height81 mm
Depth73 mm
Tightening torque (by circuit)Power circuit: 2 N.m upside 2 N.m downside
24629 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...70 °C
24629 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2 EN 60898
MPN
24629