Skip to main content
Schneider Electric 24745A — 2-Pole MCB (DIN Rail)

Schneider Electric 24745A

MPN24745A
Active

C60 - circuit breaker - C60H - 2P - 63A - B curve

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jun 2026

Specifications

24745A — Identification
ParameterValue
Product nameC60
Product rangeC60
Series / familyMulti9
Device short nameC60H
Product / component typeMiniature circuit-breaker
Device applicationDistribution
24745A — Electrical
ParameterValue
Rated current [In]63 A at 30 °C
Number of protected poles2
Pole configuration2P
Rated operational voltage [Ue]440 V AC 50/60 Hz 230...240 V AC 50/60 Hz 400...415 V AC 50/60 Hz 230/400 V AC 50/60 Hz
Network type (AC/DC)AC DC
Network frequency50/60 Hz
24745A — Protection
ParameterValue
Tripping curve codeB
Magnetic tripping limit3...5 x In
Breaking capacity (Icu)10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10000 A Icn at 230/400 V AC 50/60 Hz conforming to EN 60898 25 kA Icu at 125 V DC 2P conforming to EN/IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to EN/IEC 60947-2 50 kA Icu at <= 250 V DC 4P conforming to EN/IEC 60947-2
Rated service breaking capacity [Ics]7.5 kA conforming to EN/IEC 60947-2 - 400...415 V AC 50/60 Hz 7500 A conforming to EN 60898 - 230/400 V AC 50/60 Hz 15 kA conforming to EN/IEC 60947-2 - 230...240 V AC 50/60 Hz 5 kA conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
Energy limitation class3 conforming to EN/IEC 60947-2
Suitable for isolationYes conforming to IEC 60947-2
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
24745A — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height81 mm
Depth73 mm
Mounting support35 mm symmetrical DIN rail
Mounting modeClip-on
Terminal connectionsTunnel type terminals25 mm² flexible Tunnel type terminals35 mm² rigid
Terminal tightening torquePower circuit: 3.5 N.m upside 3.5 N.m downside
Comb busbar / distribution block compatibilityNO
Local signalling / indicationON/OFF indication
Contact position indicatorYes
24745A — Environmental
ParameterValue
Operating temperature range-25...60 °C
Storage temperature range-40...70 °C
Relative humidity95 % at 55 °C
24745A — Approvals
ParameterValue
Standards / complianceEN 60898 EN/IEC 60947-2
MPN