Skip to main content
Schneider Electric 24760 — 1-Pole MCB (DIN Rail)

Schneider Electric 24760

MPN24760
Obsolete

C60 - circuit breaker - C60H - 1P - 4A - B curve

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

24760 — Identification
ParameterValue
Product nameC60
Product / component typeMiniature circuit-breaker
Product rangeMulti9
Device short nameC60H
Poles description1P
Number of protected poles1
Device applicationDistribution
24760 — Electrical & Protection
ParameterValue
Rated current (In)4 A at 30 °C
Rated operational voltage (Ue)230...240 V AC 50/60 Hz 400...415 V AC 50/60 Hz 130 V AC 50/60 Hz
Tripping curve codeB
Magnetic tripping limit3...5 x In
Breaking capacity (Icu / AIR)30 kA Icu at 130 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 230...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 60 V DC 1P conforming to EN/IEC 60947-2 4 kA Icu at 400...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
24760 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid
Mounting support35 mm symmetrical DIN rail
Mounting modeClip-on
Width18 mm
Height81 mm
Depth73 mm
24760 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...70 °C
MPN
24760