Schneider Electric 29471
MPN29471
Active
ACP&BA controller, remote control unit for TransferPacT, 380-415V 50/60Hz, 440V 60Hz,
$1,262.34 – $2,355.48Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jun 2026
Specifications
| Parameter | Value |
|---|---|
| Product type | Interface and control unit |
| Product range | Compact NS100...630 MasterPact NT NSX400...630 Compact NS630b...1600 MasterPact NW NSX100...250 |
| Parameter | Value |
|---|---|
| Rated operational current (Ie) | AC-12: 4 A AC 440 V AC-12: 5 A AC 380/415 V AC-12: 8 A AC 110 V AC-12: 8 A AC 220/240 V AC-12: 8 A AC 24 V AC-12: 8 A AC 48 V AC-13: 6 A AC 110 V AC-13: 6 A AC 220/240 V AC-13: 7 A AC 24 V AC-13: 7 A AC 48 V AC-14: 4 A AC 110 V AC-14: 4 A AC 220/240 V AC-14: 5 A AC 24 V AC-14: 5 A AC 48 V AC-15: 3 A AC 220/240 V AC-15: 4 A AC 110 V AC-15: 5 A AC 24 V AC-15: 5 A AC 48 V DC-12: 0.4 A DC 250 V DC-12: 0.6 A DC 110 V DC-12: 2 A DC 48 V DC-12: 8 A DC 24 V DC-13: 2 A AC 24 V |
| Parameter | Value |
|---|---|
| IP degree of protection | IP20 connectors: conforming to EN 60529 IP40 front: conforming to EN 60529 IP30 side: conforming to EN 60529 |
| Parameter | Value |
|---|---|
| Standards | IEC 947-5-1 |
| Parameter | Value |
|---|---|
| Input type | Contacts customer voluntary order to transfer to source R |
| Output signal | Contacts customer: indication of operation in automatic or stop mode |
| Test function | By opening the P25M circuit breaker supplying the controller |
| Operating mode | Automatic operation Stop (both normal and replacement source off) Forced operation on replacement source Forced operation on normal source |
| Selection modes | Circuit breaker on N Circuit breaker on R |
| Local signalling | On Fault trip Off |
| Device short name | ACP + BA |
| Interlocked device | MasterPact NW MasterPact NT NSX100...250 Compact NS630b...1600 NSX400...630 Compact NS100...630 |
| Complementary function | Voluntary transfer to replacement source (e.g. energy management commands) Additional contact: transfer to replacement source only if contact is closed |
| IK degree of protection | Front: IK07 conforming to EN 50102 |
| Supply voltage | 380...415 V AC at 50/60 Hz 440 V AC at 60 Hz |
| Accessory (separate part category) | Interlocking accessory |
| [Ith] conventional free air thermal current | 8 A |
MPN
29471