Skip to main content
Schneider Electric 47212

Schneider Electric 47212

MPN47212
Active

circuit breaker Masterpact NT08L1 - 800 A - 3 poles - drawout - w/o trip unit

$3,135.51Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

47212 key specifications
ParameterValue
Control typePush-button
Performance typeL1 130 kA 440 V AC
Product or component typeCircuit breaker
Voltage1000 V AC 50/60 Hz
[Ue] rated operational voltage690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage12 kV
[Icw] rated short-time withstand current10 kA 0.5 s
Current800 A at 40 °C
[Ics] rated service breaking capacity150 kA at 220/415 V AC 50/60 Hz 130 kA at 440 V AC 50/60 Hz 100 kA at 525 V AC 50/60 Hz
[Icm] rated short-circuit making capacity330 kA 220/415 V AC at 50/60 Hz 286 kA 440 V AC at 50/60 Hz 220 kA 525 V AC at 50/60 Hz 52 kA 690 V AC at 50/60 Hz
[Icu] rated ultimate short-circuit breaking capacity150 kA at 220/415 V AC 50/60 Hz 130 kA at 440 V AC 50/60 Hz 100 kA at 525 V AC 50/60 Hz
Power dissipation in140 W

All specifications

47212 additional specifications
ParameterValue
Poles description3P
IP degree of protectionIP30 conforming to IEC 60529
Mounting modeDrawout
Mounting supportBackplate Rails
Connection pitch70 mm
Upside connectionFront Rear
Downside connectionFront Rear
Maximum closing response time50 ms
Pollution degree3 conforming to IEC 60664-1
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
Depth277 mm
Width288 mm
Height322 mm
Product weight30 kg
Electrical durability3000 cycles 440 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-2 2000 cycles 690 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-2
Mechanical durability12500 cycles without maintenance
StandardsEN/IEC 60947-1 EN/IEC 60947-2
RangeMasterPacT
Control unitWithout control unit
Sensor rating400 A 800 A
Device applicationPower distribution protection
Circuit breaker nameMasterPact NT08L1
Selectivity categoryCategory A
Maximum breaking time9 ms
Suitability for isolationYes conforming to EN/IEC 60947-2
Ambient air temperature for storage-40...85 °C
Ambient air temperature for operation-25...70 °C
Integrated instantaneous protection (DIN in kA peak)7.2...8.8 kA
MPN