Skip to main content
Schneider Electric 47237 — Air Circuit Breakers

Schneider Electric 47237

MPN47237
Active

circuit breaker Masterpact NT12H2 - 1250 A - 4 poles - drawout - w/o trip unit (Planned discontinuation end of 2025, has been replaced by LV947237)

$4,421.19Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jun 2026

Specifications

47237 — Identification
ParameterValue
Product typeCircuit breaker
Product nameMasterPact NT
RangeMasterPacT
Circuit breaker nameMasterPact NT12H2
ApplicationPower distribution protection
Control unitWithout control unit
47237 — Electrical ratings
ParameterValue
Rated current (In)1250 A at 40 °C
Sensor rating630 A 1250 A
Rated operational voltage (Ue)690 V AC 50/60 Hz
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)12 kV
Suitable for isolationYes conforming to EN/IEC 60947-2
47237 — Breaking & withstand capacity
ParameterValue
Rated ultimate breaking capacity (Icu)50 kA at 220/415 V AC 50/60 Hz 50 kA at 440 V AC 50/60 Hz 42 kA at 525 V AC 50/60 Hz 42 kA at 690 V AC 50/60 Hz
Rated service breaking capacity (Ics)42 kA at 220/415 V AC 50/60 Hz 42 kA at 440 V AC 50/60 Hz 50 kA at 525 V AC 50/60 Hz 50 kA at 690 V AC 50/60 Hz
Rated short-time withstand current (Icw)42 kA 0.5 s 42 kA 1 s 20 kA 3 s
Rated short-circuit making capacity (Icm)105 kA 220/415 V AC at 50/60 Hz 105 kA 440 V AC at 50/60 Hz 88 kA 525 V AC at 50/60 Hz 88 kA 690 V AC at 50/60 Hz
Performance typeH2 50 kA 440 V AC
47237 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.50 ms
Mechanical durability (cycles)12500 cycles without maintenance
Electrical durability (cycles)6000 cycles 440 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-2 3000 cycles 690 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-2 AC-23A: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-3 AC-23A: 3000 cycles 690 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-3
Selectivity categoryCategory B
Power dissipation250 W
47237 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportBackplate Rails
Width358 mm
Height322 mm
Depth277 mm
Neutral pole positionLeft
Connection pitch70 mm
Upside connectionFront Rear
Downside connectionFront Rear
47237 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP30 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
47237 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-2
MPN
47237