Control unit MicroLogic 6.0P, MasterPact NT drawout, selective and earth fault protections (LSIG), power meter

$3,857.21Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

47298 key specifications
ParameterValue
Display typeDigital display
Network typeAC
Protection typefor overload protection (long time) for short time short-circuit protection for instantaneous short-circuit protection for earth fault
Range of productMasterPact NT
Type of measurementPower meter
Product or component typeControl unit
Long-time protection delay adjustment type trAdjustable 9 settings
Short-time protection delay adjustment type tsdAdjustable
Short-time protection pick-up adjustment type isdAdjustable 9 settings
Ground-fault protection pick-up adjustment type igAdjustable 9 settings
Instantaneous protection pick-up adjustment type iiAdjustable 9 settings
Ground-fault protection time delay adjustment type tgAdjustable

All specifications

47298 additional specifications
ParameterValue
Long-time pick-up adjustment type ir (thermal protection)Adjustable 9 settings
Network frequency50/60 Hz
Poles3P 4P
Protected poles description4t 3t 3t + N/2
Communication of dataMeasurement readout Protection and alarm settings Maintenance indicators
Circuit breaker mounting modeDrawout
RangeMasterPact
Thermal memory20 mn
Trip unit nameMicroLogic 6.0 P
Local signalling3 LEDs (red) for electrical fault 1 LED (red) for internal error
Trip unit rating630 A at 50 °C 800 A at 50 °C 1000 A at 50 °C 1250 A at 50 °C 1600 A at 50 °C
Device applicationDistribution
Trip unit technologyElectronic
Earth-leakage protectionWithout
Trip unit protection functionsSelective + earth-fault protection
Zone selective interlocking ZSIWith
Ambient air temperature for storage-40...85 °C
Ambient air temperature for operation-25...70 °C
[Tr] Long-Time protection delay adjustment range0.7...16.6 s at 7.2 x Ir 0.7...24 s at 6 x Ir 12.5...600 s at 1.5 x Ir
[Ir] long-time protection pick-up adjustment range0.4...1 x In
[tsd] short-time protection delay adjustment range0...0.4 s I²t=off 0.1...0.4 s I²t=on
[Isd] short-time protection pick-up adjustment range1.5...10 x Ir
[Ig] ground-fault protection pick-up adjustment range0.2...1 x In for 400 A < In < 1250 A 0.3...1 x In for In 500...1200 A for In >= 1250 A
[Ii] instantaneous protection pick-up adjustment range2...15 x In Off
[Tg] Ground-Fault protection time delay adjustment range0...0.4 s I²t=off 0.1...0.4 s I²t=on
MPN