Schneider Electric 48309 — Air Circuit Breakers

Schneider Electric 48309

MPN48309
Active

circuit breaker Masterpact NW25H2 - 2500 A - 4 poles - drawout - w/o trip unit

$10,348.42Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jun 2026

Specifications

48309 — Identification
ParameterValue
Product typeCircuit breaker
Product nameMasterPact NW
RangeMasterPacT
Circuit breaker nameMasterPact NW25H2
ApplicationPower distribution protection
Control unitWithout control unit
48309 — Electrical ratings
ParameterValue
Rated current (In)2500 A at 40 °C
Sensor rating1250 A 2500 A
Rated operational voltage (Ue)690 V AC 50/60 Hz
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)12 kV
Suitable for isolationYes conforming to EN/IEC 60947-2
48309 — Breaking & withstand capacity
ParameterValue
Rated ultimate breaking capacity (Icu)100 kA at 220/415 V AC 50/60 Hz 100 kA at 440 V AC 50/60 Hz 85 kA at 525 V AC 50/60 Hz 85 kA at 690 V AC 50/60 Hz
Rated service breaking capacity (Ics)100 kA at 220/415 V AC 50/60 Hz 100 kA at 440 V AC 50/60 Hz 85 kA at 525 V AC 50/60 Hz 85 kA at 690 V AC 50/60 Hz
Rated short-time withstand current (Icw)85 kA 1 s 75 kA 3 s
Rated short-circuit making capacity (Icm)220 kA 220/415 V AC at 50/60 Hz 187 kA 440 V AC at 50/60 Hz 187 kA 525 V AC at 50/60 Hz 187 kA 690 V AC at 50/60 Hz
Performance typeH2 100 kA 440 V AC
48309 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)10000 cycles without maintenance 20000 cycles with maintenance
Electrical durability (cycles)5000 cycles 440 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-2 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-2 AC-23A: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-3 AC-23A: 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-3
Selectivity categoryCategory B
Power dissipation600 W
48309 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportBackplate Rails
Width556 mm
Height439 mm
Depth395 mm
Neutral pole positionRight
Connection pitch115 mm
Upside connectionFront Rear
Downside connectionFront Rear
48309 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP30 conforming to IEC 60529
Pollution degree4 conforming to IEC 60664-1
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
48309 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-2
MPN