Specifications

48667 — Identification
ParameterValue
Product typeCircuit breaker
Product nameMasterPact NW DC
RangeMasterPacT
Circuit breaker nameMasterPact NW20HDC-D
ApplicationDC voltage switching
Control unitWithout control unit
48667 — Electrical ratings
ParameterValue
Rated current (In)2000 A at 40 °C
Sensor rating2000 A
Rated operational voltage (Ue)500/900 V DC
Poles3P
Rated insulation voltage (Ui)1000 V DC
Rated impulse withstand voltage (Uimp)12 kV
Suitable for isolationYes conforming to EN/IEC 60947-2
48667 — Breaking & withstand capacity
ParameterValue
Rated ultimate breaking capacity (Icu)100 kA Icu at 500 V DC L/R = 5 ms 25 kA Icu at 900 V DC L/R = 30 ms 35 kA Icu at 900 V DC L/R = 15 ms 50 kA Icu at 500 V DC L/R = 30 ms 50 kA Icu at 750 V DC L/R = 15 ms 50 kA Icu at 750 V DC L/R = 30 ms 85 kA Icu at 500 V DC L/R = 15 ms 85 kA Icu at 750 V DC L/R = 5 ms 85 kA Icu at 900 V DC L/R = 5 ms
Rated service breaking capacity (Ics)100 kA at 500 V DC (L/R = 5 ms) 25 kA at 900 V DC (L/R = 30 ms) 35 kA at 900 V DC (L/R = 15 ms) 50 kA at 500 V DC (L/R = 30 ms) 50 kA at 750 V DC (L/R = 15 ms) 50 kA at 750 V DC (L/R = 30 ms) 85 kA at 500 V DC (L/R = 15 ms) 85 kA at 750 V DC (L/R = 5 ms) 85 kA at 900 V DC (L/R = 5 ms)
Rated short-time withstand current (Icw)85 kA 1 s
Rated short-circuit making capacity (Icm)100 kA L/R = 5 ms 500 V DC 25 kA L/R = 30 ms 900 V DC 35 kA L/R = 15 ms 900 V DC 50 kA L/R = 30 ms 500 V DC 50 kA L/R = 15 ms 750 V DC 50 kA L/R = 30 ms 750 V DC 85 kA L/R = 15 ms 500 V DC 85 kA L/R = 5 ms 750 V DC 85 kA L/R = 5 ms 900 V DC
Performance typeH 85 kA 500 V DC
48667 — Performance
ParameterValue
Breaking time, max.30...75 ms
Closing response time, max.70 ms
Mechanical durability (cycles)10000 cycles without maintenance conforming to IEC 60947-2 20000 cycles with maintenance conforming to IEC 60947-2
Electrical durability (cycles)5000 cycles 500 V DC without maintenance conforming to IEC 60947-2 2000 cycles 900 V DC without maintenance conforming to IEC 60947-2
Selectivity categoryCategory B
Power dissipation2000 W
48667 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportBackplate Rails
Width441 mm
Height439 mm
Depth494 mm
Connection pitch115 mm
Upside connectionRear
Downside connectionRear
48667 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
Pollution degree4 conforming to IEC 60664-1
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
48667 — Approvals
ParameterValue
StandardsIEC 60947-2
MPN
48667