Skip to main content
Schneider Electric 49553 — Fuses & Fuse Holders

Schneider Electric 49553

MPN49553
Obsolete

Switch-disconnector fuse body INFD 3 poles 3F - DIN - 400 A- front handle

$437.88Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

49553 — Identification
ParameterValue
Product nameFupact INF
Product / component typeSwitch-disconnector-fuse
Fuse typeDIN
Poles3P
ApplicationProtection
Product range / familyFuPact
Product rangeINF200...800
49553 — Ratings
ParameterValue
Rated operational voltage (Ue)690 V AC 50/60 Hz 1000 V AC 50/60 Hz AC-20 1000 V DC DC-20 750 V DC
Rated operational current (Ie)AC-22A: 400 A at 220/240 V AC 50/60 Hz AC-22A: 400 A at 380/415 V AC 50/60 Hz AC-22A: 400 A at 440/480 V AC 50/60 Hz AC-22A: 400 A at 500/525 V AC 50/60 Hz AC-22A: 400 A at 660/690 V AC 50/60 Hz AC-23A: 400 A at 220/240 V AC 50/60 Hz AC-23A: 400 A at 380/415 V AC 50/60 Hz AC-23A: 400 A at 440/480 V AC 50/60 Hz AC-23A: 400 A at 500/525 V AC 50/60 Hz AC-23A: 400 A at 660/690 V AC 50/60 Hz DC-22A: 400 A at 125 V DC (2 poles in series) DC-22A: 400 A at 250 V DC (2 poles in series) DC-22A: 400 A at 500 V DC (3 poles in series) DC-22A: 400 A at 750 V DC (3 poles in series) DC-23A: 400 A at 125 V DC (2 poles in series) DC-23A: 400 A at 250 V DC (2 poles in series) DC-23A: 400 A at 500 V DC (3 poles in series) DC-23A: 400 A at 750 V DC (3 poles in series)
Rated insulation voltage (Ui)1000 V AC 50/60 Hz 1000 V DC
Rated impulse withstand voltage (Uimp)12 kV
Conventional free-air thermal current (Ith)268 A ( 70 °C ) horizontal 277 A ( 65 °C ) horizontal 280 A ( 70 °C ) vertical 295 A ( 60 °C ) horizontal 300 A ( 65 °C ) vertical 313 A ( 55 °C ) horizontal 320 A ( 60 °C ) vertical 331 A ( 50 °C ) horizontal 340 A ( 55 °C ) vertical 350 A ( 45 °C ) horizontal 360 A ( 50 °C ) vertical 368 A ( 40 °C ) horizontal 380 A ( 45 °C ) vertical 386 A ( 35 °C ) horizontal 400 A ( 40 °C ) power dissipation per fuse: 45 W 400 A ( 40 °C ) vertical
Conventional enclosed thermal current (Ithe)360 A at 40 °C, Power dissipation per fuse: 37 W (500 mm x 400 mm x 250 mm) 400 A at 40 °C, Power dissipation per fuse: 34 W (500 mm x 400 mm x 250 mm)
Network frequency50/60 Hz
Network type (AC/DC)DC AC
Maximum power110 kW at 220/240 V AC 50/60 Hz 210 kW at 380/400 V AC 50/60 Hz 230 kW at 415 V AC 50/60 Hz 280 kW at 500/525 V AC 50/60 Hz 330 kW at 660/690 V AC 50/60 Hz
49553 — Protection & Breaking
ParameterValue
Suitable for isolationYes
Contact operationDouble-break
Rated short-time withstand current (Icw)10 kA for 1 s 1.85 kA for 30 s 2.25 kA for 20 s 5.8 kA for 3 s
Rated making & breaking capacity (Im)Icm 105 kA at 690 V conforming to DIN (with fuse) Icm 176 kA at 415 V conforming to BS (with fuse) Icm 220 kA at 500 V conforming to DIN (with fuse) Icn 100 kA at 500 V conforming to DIN (with fuse) Icn 50 kA at 690 V conforming to DIN (with fuse) Icn 80 kA at 415 V conforming to BS (with fuse) Icm 35 kA at 690 V (without fuse) Icm 40 kA at 415 V (without fuse) Icm 40 kA at 500 V (without fuse)
Contact position indicatorYes
Protected poles3f
49553 — Performance
ParameterValue
Mechanical durability (cycles)8000 cycles
Electrical durability (cycles)AC-22A: 1000 cycles 500 V AC 50/60 Hz AC-22A: 1000 cycles 690 V AC 50/60 Hz AC-23A: 1000 cycles 500 V AC 50/60 Hz AC-23A: 1000 cycles 690 V AC 50/60 Hz
Control typeRotary handle
Rated dutyUninterrupted
Intermittent duty classClass 120 - 60 %
49553 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP protection ratingIP20 conforming to IEC 60529 IP65 conforming to IEC 60529
IK impact protection ratingIK07 conforming to EN 50102 IK10 conforming to EN 50102
Pollution degree3
49553 — Mechanical
ParameterValue
Mounting supportMounting plate
Fuse sizeNH1 NH2 NH0
Width302 mm
Depth206 mm
Height180 mm
Tightening torque30...44 N.m for terminal
Rotary handle mounting styleExtended Direct
49553 — Approvals
ParameterValue
Standards / approvalsEN/IEC 60947-5 EN/IEC 60947-1 EN/IEC 60269-1 EN/IEC 60269-4 EN/IEC 60947-3
49553 — Specifications
ParameterValue
Device short nameINFD400
MPN
49553