Skip to main content
Schneider Electric 49581 — Fuses & Fuse Holders

Schneider Electric 49581

MPN49581
Active

Switch-disconnector fuse body INFB 3 poles 3F - BS - 100 A- front handle

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jun 2026

Specifications

49581 — Identification
ParameterValue
Product nameFupact INF
Product / component typeSwitch-disconnector-fuse
Fuse typeBS
Poles3P
ApplicationProtection
Product range / familyFuPact
Product rangeINF100...160
49581 — Ratings
ParameterValue
Rated operational voltage (Ue)690 V AC 50/60 Hz 690 V AC 50/60 Hz AC-20 690 V DC DC-20 500 V DC
Rated operational current (Ie)DC-22A: 100 A at 500 V DC (4 poles in series) DC-23A: 100 A at 500 V DC (4 poles in series) AC-22A: 100 A at 220/240 V AC 50/60 Hz AC-22A: 100 A at 380/415 V AC 50/60 Hz AC-22A: 100 A at 440/480 V AC 50/60 Hz AC-22A: 100 A at 500/525 V AC 50/60 Hz AC-22A: 100 A at 660/690 V AC 50/60 Hz AC-23A: 100 A at 220/240 V AC 50/60 Hz AC-23A: 100 A at 380/415 V AC 50/60 Hz AC-23A: 100 A at 440/480 V AC 50/60 Hz AC-23A: 100 A at 500/525 V AC 50/60 Hz AC-23B: 100 A at 660/690 V AC 50/60 Hz DC-22A: 100 A at 125 V DC (2 poles in series) DC-22A: 100 A at 250 V DC (2 poles in series) DC-23A: 100 A at 125 V DC (2 poles in series) DC-23A: 100 A at 250 V DC (2 poles in series)
Rated insulation voltage (Ui)1000 V AC 50/60 Hz 1000 V DC
Rated impulse withstand voltage (Uimp)12 kV
Conventional free-air thermal current (Ith)100 A ( 40 °C ) power dissipation per fuse: 12 W 100 A ( 40 °C ) vertical 65 A ( 70 °C ) horizontal 69 A ( 65 °C ) horizontal 70 A ( 70 °C ) vertical 74 A ( 60 °C ) horizontal 75 A ( 65 °C ) vertical 78 A ( 55 °C ) horizontal 80 A ( 60 °C ) vertical 83 A ( 50 °C ) horizontal 85 A ( 55 °C ) vertical 87 A ( 45 °C ) horizontal 90 A ( 50 °C ) vertical 92 A ( 40 °C ) horizontal 95 A ( 45 °C ) vertical 96 A ( 35 °C ) horizontal
Conventional enclosed thermal current (Ithe)100 A at 40 °C, Power dissipation per fuse: 12 W (300 mm x 350 mm x 200 mm)
Network frequency50/60 Hz
Network type (AC/DC)DC AC
Maximum power30 kW at 220/240 V AC 50/60 Hz 45 kW at 380/400 V AC 50/60 Hz 55 kW at 415 V AC 50/60 Hz 60 kW at 500/525 V AC 50/60 Hz 90 kW at 660/690 V AC 50/60 Hz
49581 — Protection & Breaking
ParameterValue
Suitable for isolationYes
Contact operationDouble-break
Rated short-time withstand current (Icw)5 kA for 1 s 0.95 kA for 30 s 1.15 kA for 20 s 2.9 kA for 3 s
Rated making & breaking capacity (Im)Icm 105 kA at 690 V conforming to DIN (with fuse) Icm 176 kA at 415 V conforming to BS (with fuse) Icm 220 kA at 500 V conforming to DIN (with fuse) Icn 100 kA at 500 V conforming to DIN (with fuse) Icn 50 kA at 690 V conforming to DIN (with fuse) Icn 80 kA at 415 V conforming to BS (with fuse) Icm 15 kA at 690 V (without fuse) Icm 22 kA at 415 V (without fuse) Icm 22 kA at 500 V (without fuse)
Contact position indicatorYes
Protected poles3f
49581 — Performance
ParameterValue
Mechanical durability (cycles)10000 cycles
Electrical durability (cycles)AC-22A: 1500 cycles 500 V AC 50/60 Hz AC-22A: 1500 cycles 690 V AC 50/60 Hz AC-23A: 1500 cycles 500 V AC 50/60 Hz AC-23A: 1500 cycles 690 V AC 50/60 Hz
Control typeWithout handle
Rated dutyUninterrupted
Intermittent duty classClass 120 - 60 %
49581 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP protection ratingIP20 conforming to IEC 60529 IP65 conforming to IEC 60529
IK impact protection ratingIK07 conforming to EN 50102 IK10 conforming to EN 50102
Pollution degree3
49581 — Mechanical
ParameterValue
Mounting supportDIN rail, with specific accessories Mounting plate
Fuse sizeA2 A4 A3
Width180 mm
Depth130 mm
Height140 mm
Tightening torque15...22 N.m for terminal
Rotary handle mounting styleExtended Direct
49581 — Approvals
ParameterValue
Standards / approvalsEN/IEC 60947-3 EN/IEC 60947-1 EN/IEC 60269-4 EN/IEC 60947-5 EN/IEC 60269-1
49581 — Specifications
ParameterValue
Device short nameINFB100
MPN
49581