Schneider Electric 49584
MPN49584
Obsolete
Switch-disconnector fuse body INFB 4 poles 3F - BS - 100 A- lateral handle
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jun 2026
Specifications
Identification
| Parameter | Value |
|---|---|
| Product name | Fupact INF |
| Product / component type | Switch-disconnector-fuse |
| Fuse type | BS |
| Poles | 4P |
| Application | Protection |
| Product range / family | FuPact |
| Product range | INF100...160 |
Ratings
| Parameter | Value |
|---|---|
| Rated operational voltage (Ue) | 690 V AC 50/60 Hz 690 V AC 50/60 Hz AC-20 690 V DC DC-20 500 V DC |
| Rated operational current (Ie) | DC-22A: 100 A at 500 V DC (4 poles in series) DC-23A: 100 A at 500 V DC (4 poles in series) AC-22A: 100 A at 220/240 V AC 50/60 Hz AC-22A: 100 A at 380/415 V AC 50/60 Hz AC-22A: 100 A at 440/480 V AC 50/60 Hz AC-22A: 100 A at 500/525 V AC 50/60 Hz AC-22A: 100 A at 660/690 V AC 50/60 Hz AC-23A: 100 A at 220/240 V AC 50/60 Hz AC-23A: 100 A at 380/415 V AC 50/60 Hz AC-23A: 100 A at 440/480 V AC 50/60 Hz AC-23A: 100 A at 500/525 V AC 50/60 Hz AC-23B: 100 A at 660/690 V AC 50/60 Hz DC-22A: 100 A at 125 V DC (2 poles in series) DC-22A: 100 A at 250 V DC (2 poles in series) DC-23A: 100 A at 125 V DC (2 poles in series) DC-23A: 100 A at 250 V DC (2 poles in series) |
| Rated insulation voltage (Ui) | 1000 V AC 50/60 Hz 1000 V DC |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Conventional free-air thermal current (Ith) | 100 A ( 40 °C ) power dissipation per fuse: 12 W 100 A ( 40 °C ) vertical 65 A ( 70 °C ) horizontal 69 A ( 65 °C ) horizontal 70 A ( 70 °C ) vertical 74 A ( 60 °C ) horizontal 75 A ( 65 °C ) vertical 78 A ( 55 °C ) horizontal 80 A ( 60 °C ) vertical 83 A ( 50 °C ) horizontal 85 A ( 55 °C ) vertical 87 A ( 45 °C ) horizontal 90 A ( 50 °C ) vertical 92 A ( 40 °C ) horizontal 95 A ( 45 °C ) vertical 96 A ( 35 °C ) horizontal |
| Conventional enclosed thermal current (Ithe) | 100 A at 40 °C, Power dissipation per fuse: 12 W (300 mm x 350 mm x 200 mm) |
| Network frequency | 50/60 Hz |
| Network type (AC/DC) | DC AC |
| Maximum power | 30 kW at 220/240 V AC 50/60 Hz 45 kW at 380/400 V AC 50/60 Hz 55 kW at 415 V AC 50/60 Hz 60 kW at 500/525 V AC 50/60 Hz 90 kW at 660/690 V AC 50/60 Hz |
Protection & Breaking
| Parameter | Value |
|---|---|
| Suitable for isolation | Yes |
| Contact operation | Double-break |
| Rated short-time withstand current (Icw) | 5 kA for 1 s 0.95 kA for 30 s 1.15 kA for 20 s 2.9 kA for 3 s |
| Rated making & breaking capacity (Im) | Icm 105 kA at 690 V conforming to DIN (with fuse) Icm 176 kA at 415 V conforming to BS (with fuse) Icm 220 kA at 500 V conforming to DIN (with fuse) Icn 100 kA at 500 V conforming to DIN (with fuse) Icn 50 kA at 690 V conforming to DIN (with fuse) Icn 80 kA at 415 V conforming to BS (with fuse) Icm 15 kA at 690 V (without fuse) Icm 22 kA at 415 V (without fuse) Icm 22 kA at 500 V (without fuse) |
| Contact position indicator | Yes |
| Protected poles | 3f |
Performance
| Parameter | Value |
|---|---|
| Mechanical durability (cycles) | 10000 cycles |
| Electrical durability (cycles) | AC-22A: 1500 cycles 500 V AC 50/60 Hz AC-22A: 1500 cycles 690 V AC 50/60 Hz AC-23A: 1500 cycles 500 V AC 50/60 Hz AC-23A: 1500 cycles 690 V AC 50/60 Hz |
| Control type | Without handle |
| Rated duty | Uninterrupted |
| Intermittent duty class | Class 120 - 60 % |
Environmental
| Parameter | Value |
|---|---|
| Operating ambient temperature | -25...70 °C |
| Storage ambient temperature | -50...85 °C |
| IP protection rating | IP20 conforming to IEC 60529 IP65 conforming to IEC 60529 |
| IK impact protection rating | IK07 conforming to EN 50102 IK10 conforming to EN 50102 |
| Pollution degree | 3 |
Mechanical
| Parameter | Value |
|---|---|
| Mounting support | DIN rail, with specific accessories Mounting plate |
| Fuse size | A3 A2 A4 |
| Width | 215 mm |
| Depth | 130 mm |
| Height | 140 mm |
| Tightening torque | 15...22 N.m for terminal |
| Rotary handle mounting style | Extended |
Approvals
| Parameter | Value |
|---|---|
| Standards / approvals | EN/IEC 60947-3 EN/IEC 60269-1 EN/IEC 60269-4 EN/IEC 60947-1 EN/IEC 60947-5 |
Specifications
| Parameter | Value |
|---|---|
| Device short name | INFB100 |
MPN
49584