Schneider Electric 56233
MPN56233
Active
residual current protection relay, Vigirex RH10P, 115 mA, 220/240 VAC 50/60 Hz, front panel mounting
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jun 2026
Specifications
Residual Current Protection
| Parameter | Value |
|---|---|
| Earth-leakage sensitivity (IΔn) | 0.115 A |
| Earth-leakage protection class / type | Type A |
Electrical Ratings
| Parameter | Value |
|---|---|
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Overvoltage category | IV |
Identification
| Parameter | Value |
|---|---|
| Product / component type | Residual current protection relay |
| Product range / family | Vigirex |
| Device short name | RH10P |
Mechanical
| Parameter | Value |
|---|---|
| Mounting support | Front panel |
| Terminal connections | Auxiliary power supply: terminal block cable(s) 0.2...2.5 mm² flexible AWG 24...AWG 12 Auxiliary power supply: terminal block cable(s) 0.2...2.5 mm² rigid AWG 24...AWG 12 Auxiliary power supply: terminal block cable(s) 0.25...2.5 mm² flexible AWG 24...AWG 12 Fault: terminal block cable(s) 0.2...2.5 mm² flexible AWG 24...AWG 12 Fault: terminal block cable(s) 0.2...2.5 mm² rigid AWG 24...AWG 12 Fault: terminal block cable(s) 0.25...2.5 mm² flexible AWG 24...AWG 12 Relay test and fault reset: terminal block cable(s) 0.2...2.5 mm² flexible AWG 24...AWG 12 Relay test and fault reset: terminal block cable(s) 0.2...2.5 mm² rigid AWG 24...AWG 12 Relay test and fault reset: terminal block cable(s) 0.25...2.5 mm² flexible AWG 24...AWG 12 Sensor: terminal block cable(s) 0.2...2.5 mm² flexible AWG 24...AWG 12 Sensor: terminal block cable(s) 0.2...2.5 mm² rigid AWG 24...AWG 12 Sensor: terminal block cable(s) 0.25...2.5 mm² flexible AWG 24...AWG 12 Voltage presence: terminal block cable(s) 0.2...2.5 mm² flexible AWG 24...AWG 12 Voltage presence: terminal block cable(s) 0.2...2.5 mm² rigid AWG 24...AWG 12 Voltage presence: terminal block cable(s) 0.25...2.5 mm² flexible AWG 24...AWG 12 |
| Wire stripping length | Auxiliary power supply: 7 mm Fault: 7 mm Relay test and fault reset: 7 mm Sensor: 7 mm Voltage presence: 7 mm |
| Terminal tightening torque | Auxiliary power supply: 0.6 N.m Fault: 0.6 N.m Relay test and fault reset: 0.6 N.m Sensor: 0.6 N.m Voltage presence: 0.6 N.m |
| Width | 72 mm |
| Height | 72 mm |
| Depth | 78 mm |
Environmental
| Parameter | Value |
|---|---|
| Operating ambient temperature | -35...70 °C |
| Storage ambient temperature | -55...85 °C |
| IP degree of protection | IP40 on front face: conforming to EN/IEC 60529 IP30 on side parts: conforming to EN/IEC 60529 IP20 on connection terminals: conforming to EN/IEC 60529 |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Relative humidity | 95 % at 55 °C |
Approvals
| Parameter | Value |
|---|---|
| Standards | EN/IEC 60947-2 Annex M EN/IEC 60755 UL 1053 CAN/CSA C22.2 No. 144 |
MPN
56233