Schneider Electric 56502
MPN56502
Obsolete
Residual current protection relay, VigiPacT RH86P, 30mA to 10A, 220/240VAC 50/60Hz, front panel mounting
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Earth-leakage sensitivity (IΔn) | 0.03...10 A |
| Earth-leakage protection class / type | Type A |
| Parameter | Value |
|---|---|
| Rated impulse withstand voltage (Uimp) | 8 kV |
| Overvoltage category | IV |
| Parameter | Value |
|---|---|
| Product / component type | Residual current protection relay |
| Product range / family | VigiPacT |
| Parameter | Value |
|---|---|
| Mounting support | Front panel |
| Wire stripping length | Auxiliary power supply: 7 mm for top connection Fault: 8 mm for bottom connection Relay test and fault reset: 5 mm for bottom connection Sensor: 5 mm for top connection Voltage presence: 8 mm for bottom connection |
| Terminal tightening torque | Auxiliary power supply: 0.6 N.m top Fault: 0.6 N.m bottom Relay test and fault reset: 0.25 N.m bottom Sensor: 0.25 N.m top Voltage presence: 0.6 N.m bottom |
| Width | 72 mm |
| Height | 72 mm |
| Depth | 78 mm |
| Parameter | Value |
|---|---|
| Operating ambient temperature | -35...70 °C |
| Storage ambient temperature | -55...85 °C |
| IP degree of protection | IP40 on front face: conforming to EN/IEC 60529 IP30 on side parts: conforming to EN/IEC 60529 IP20 on connection terminals: conforming to EN/IEC 60529 |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Relative humidity | 95 % at 55 °C |
| Parameter | Value |
|---|---|
| Standards | EN/IEC 60947-2 Annex M EN/IEC 60755 UL 1053 CAN/CSA C22.2 No. 144 |
MPN
56502