Skip to main content
Schneider Electric A9C15506 — Contactors

Schneider Electric A9C15506 Acti9 TL Impulse Relay, 16 A, 1P

MPNA9C15506
Obsolete

Schneider Electric Acti9 TL impulse relay, A9C15506, 1P, 16 A rated, 230 V AC 50 Hz control, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9C15506 — Identification
ParameterValue
Product / component typeImpulse relay
A9C15506 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)250 V AC 50 Hz
A9C15506 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529 (on opening) IP40 conforming to IEC 60529 (in enclosure)
A9C15506 — Approvals
ParameterValue
StandardsIEC 60669-2-2 IEC 60669-1
A9C15506 — Mechanical
ParameterValue
Width18 mm
Height84 mm
Depth60 mm

Product details

The Schneider Electric A9C15506 is an Acti9 TL impulse relay — a 1-pole, 16 A rated device for switching lighting and resistive loads on 230 V AC 50 Hz networks. It's a latching relay: a 50 ms impulse on the control circuit toggles the NO contact, and it holds that state without coil power draw. The 19 VA hold-in consumption is only during the impulse, not continuous. Rated for AC-22 duty at 200,000 cycles, this covers mixed resistive and inductive loads up to 16 A — typical for contactor-driven lighting banks, fan coils, and general building automation switching. The 5 operations/minute switching frequency matches the pulse-repeat rate of push-button or PLC impulse control.

Snaps onto standard DIN rail, occupying 18 mm width (one modular pitch). The 84 mm height and 60 mm depth fit flush in a distribution board or enclosure alongside Acti9 MCBs and RCCBs. IP20 on the opening, IP40 inside the enclosure — so it's panel-protected, not for wet locations. Terminals are tunnel type: power circuit accepts 1 or 2 cables up to 4 mm² rigid or 2.5 mm² flexible (with or without ferrule). Control circuit takes 1 cable up to 1.5 mm². Strip length is 9 mm; tighten to 1 N·m. The NO contact composition means one switched pole per unit — if you need multiple poles, stack units with a common control impulse.

Certified to IEC 60669-2-2 and IEC 60669-1 (remote-control switching devices and general requirements). Pollution degree 3 suits industrial environments with conductive pollution. Tropicalisation class 2 means the relay is treated for humidity up to 95% at 55 °C — relevant for warm, damp panel installations. NF quality label indicates compliance with French standard NF C 61-314, often required for French-market building electrical installations.

Frequently asked questions

What are the key ratings for the A9C15506?

16 A rated current (In), 1 pole NO contact, 230 V AC 50 Hz control voltage, 250 V AC 50 Hz operational voltage. Electrical durability is 200,000 cycles at AC-22 duty. Switching frequency is 5 operations per minute.

What compliance documentation does Schneider provide for the A9C15506?

The relay is certified to IEC 60669-2-2 and IEC 60669-1, carries the NF quality label (NF C 61-314), and is rated for pollution degree 3 and tropicalisation class 2. IP20 on the opening, IP40 in enclosure per IEC 60529.

How is the A9C15506 mounted and wired?

DIN rail mount, 18 mm width (1 module). Power terminals accept 1–4 mm² rigid or 1–2.5 mm² flexible (1 or 2 cables). Control terminals accept 0.5–1.5 mm². Strip 9 mm, torque to 1 N·m.

MPN
A9C15506