Skip to main content
Schneider Electric A9C20443 — Contactors

Schneider Electric A9C20443 Acti9 iCT Contactor, 40 A AC-7A,

MPNA9C20443
Obsolete

Schneider Electric Acti9 iCT contactor, A9C20443, 3P, 40 A AC-7A / 15 A AC-7B, 127 V AC 60 Hz coil, clip-on 35 mm DIN rail, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9C20443 — Identification
ParameterValue
Product / component typeContactor
A9C20443 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)400 V AC 60 Hz
A9C20443 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Operating altitude2000 m
A9C20443 — Approvals
ParameterValue
StandardsIEC/EN 61095
A9C20443 — Mechanical
ParameterValue
Width54 mm
Height85 mm
Depth68.5 mm

Product details

It is rated for a 127 V AC 60 Hz maintained control signal and carries a 40 A AC-7A and 15 A AC-7B operational current at 400 V AC 60 Hz, per IEC/EN 61095. The AC-7A rating covers resistive and inductive loads typical of lighting and heating; the AC-7B rating covers motor loads up to 15 A. This means the contactor is sized for a 3.5 kW motor at 400 V (roughly 7.5 A full-load) with headroom on the resistive side.

Durability and switching life

Electrical durability is rated per duty: 100,000 cycles at 40 A AC-7A, 30,000 cycles at 15 A AC-7B, and 30,000 cycles for AC-3 motor switching. Mechanical durability is 1,000,000 cycles. The switching frequency is limited to 100 operations per day, which is typical for contactors in building-services duty — not for high-speed machine cycling.

Dimensions: 85 mm high, 54 mm wide, 68.5 mm deep. The 54 mm width is 3 module pitches (9 mm each). Power circuit terminals accept 6 to 25 mm² rigid or 6 to 16 mm² flexible cable; control circuit terminals accept 1.5 to 2.5 mm². Tightening torque: 3.5 N·m for power, 0.8 N·m for control. IP20 on the body, IP40 in a modular enclosure. Tropicalisation conforms to EN 60947-4-1 and EN 61095.

Frequently asked questions

What are the key ratings for A9C20443?

3-pole contactor, 40 A AC-7A / 15 A AC-7B at 400 V AC 60 Hz, 127 V AC 60 Hz coil. Electrical durability is 100,000 cycles at AC-7A, 30,000 at AC-7B. Mechanical durability is 1,000,000 cycles.

What compliance documentation does this brand provide for A9C20443?

The contactor complies with IEC/EN 61095 and EN 60947-4-1. Tropicalisation is certified to those same standards. IP20 per IEC 60529. These cover the typical CE-marking requirements for building-services panels.

What is A9C20443's listed depth?

68.5 mm.

What is A9C20443's listed poles?

3P (three poles), with 3 NO contacts.

MPN
A9C20443