It clips onto a 35 mm symmetrical DIN rail and is rated for 40 A in AC-7A duty (general-use inductive loads) and 15 A in AC-7B duty (motor loads) at 400 V AC, 50 Hz. The coil is 220-240 V AC, maintained control signal type.
The 40 A AC-7A rating covers resistive and lightly inductive loads like heating banks or lighting circuits. The 15 A AC-7B rating is the one to check for motor switching — it reflects the higher inrush and inductive break duty typical of small pumps, fans, or compressors. Electrical durability is specified per duty cycle: 100,000 cycles at 40 A AC-7A, 30,000 cycles at 15 A AC-7B, and 30,000 cycles under AC-3 (cage motor starting). Mechanical durability is 1,000,000 cycles, so the contactor outlasts its electrical life in most applications. The contactor is tropicalised (2 levels conforming to EN 60947-4-1 and EN 61095), meaning it withstands 95% relative humidity at 55 °C without performance degradation — relevant for panels in coastal or unconditioned spaces.
The 54 mm width (9 mm pitches × 6) fits standard modular enclosure spacing. Power circuit terminals accept 6-25 mm² rigid or 6-16 mm² flexible cable; control circuit terminals accept 1.5-2.5 mm². The action indicator provides local signalling of contactor state.