Skip to main content
Schneider Electric A9C52463 — Contactors

Schneider A9C52463 Reflex iC60N 63A 4P C-Curve MCB

MPNA9C52463
Obsolete

Schneider Electric Acti9 Reflex iC60N, integrated control circuit breaker, 63 A, 4P, curve C, 20 kA breaking capacity at 230 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9C52463 — Identification
ParameterValue
Product / component typeIntegrated control circuit breaker
Series / rangeActi9
A9C52463 — Contacts & Poles
ParameterValue
Pole configuration4P
A9C52463 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
A9C52463 — Mechanical
ParameterValue
Width117 mm
Height84 mm
Depth77 mm

Product details

The Schneider Electric A9C52463 is a Reflex iC60N integrated control circuit breaker from the Acti9 range — a 4-pole, 63 A, curve C thermal-magnetic MCB that also functions as a remote-controlled switching device. It combines overcurrent protection (20 kA Icu at 230 V AC per EN/IEC 60947-2) with the ability to open and close the circuit via a remote pulse, maintained signal, or local toggle, making it a single-device solution for distribution and control applications where you'd otherwise need a separate contactor and breaker.

Control and integration

The control circuit accepts multiple voltages — 230 V AC, 24 V AC, 48 V AC, 24 V DC, or 48 V DC — so you can match whatever pilot signal your PLC, pushbutton station, or building management system outputs. Control can be a pulse (momentary ON/OFF), a maintained signal (continuous command), or a local toggle, giving flexibility for remote or local switching schemes.

Durability and environmental ratings

Rated for 50,000 electrical cycles under AC-1 resistive load and 50,000 mechanical cycles — this is a device meant for regular switching duty, not just backup protection.

Frequently asked questions

What is the breaking capacity of the A9C52463?

20 kA Icu at 220–240 V AC 50/60 Hz per EN/IEC 60947-2, and 10 kA Icu at 380–415 V AC. The N breaking capacity code indicates the standard interrupting level for this Reflex iC60N variant.

What control voltages does the A9C52463 accept?

The control circuit accepts 230 V AC, 24 V AC, 48 V AC, 24 V DC, or 48 V DC — all at 50/60 Hz for AC. The control signal can be an impulse (pulse ON/OFF), a maintained signal, or a local toggle.

Does the A9C52463 include earth-leakage protection?

No, earth-leakage protection requires a separate block (Vigi or similar) — this is a thermal-magnetic MCB only, with provision for add-on RCD modules downstream.

MPN
A9C52463