Skip to main content
Schneider Electric A9C61225 — Contactors

Schneider Electric A9C61225 Reflex iC60N Ti24, 25A 2P Curve

MPNA9C61225
Active

Schneider Electric Acti9 Reflex iC60N Ti24 integrated control MCB, A9C61225, 25 A, 2P, curve B, 20 kA breaking capacity at 230 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9C61225 — Identification
ParameterValue
Product / component typeIntegrated control circuit breaker
Series / rangeActi9
A9C61225 — Contacts & Poles
ParameterValue
Pole configuration2P
A9C61225 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
A9C61225 — Mechanical
ParameterValue
Width81 mm
Height84 mm
Depth77 mm

Product details

The Schneider Electric A9C61225 is a Reflex iC60N Ti24 integrated control circuit breaker from the Acti9 range — a 2-pole thermal-magnetic MCB rated at 25 A with a B curve, designed for distribution and control applications on AC networks at 50/60 Hz. What sets this part apart from a standard MCB is the integrated control: it accepts remote control by pulse, by continuous command, or via a toggle ON/OFF button on the front face, with control circuit voltage options covering 230 V AC, 24 V AC, 48 V AC, 24 V DC, and 48 V DC. The 20 kA Icu breaking capacity at 230 V AC (10 kA at 380–415 V AC) per EN/IEC 60947-2 means it safely interrupts fault currents up to that level without the arc propagating — adequate for most commercial and light industrial distribution boards where the prospective short-circuit current stays under that threshold.

IP20 rated per IEC 60529 — suitable for enclosed panel installation where no water ingress is expected; the front face provides local signalling via a flashing LED for trip/ready/overheat states, a red LED for fault, and a green LED for device ON. Padlockable in the OFF position, with a contact position indicator, giving a visible isolation point for lockout/tagout procedures during maintenance.

Durability and environmental ratings

Rated for 50,000 electrical cycles under AC-1 resistive load and 50,000 mechanical cycles — the electrical endurance is the binding constraint for frequent switching applications like lighting or contactor replacement. Tropicalisation class 2 adds corrosion resistance for humid environments up to 93% relative humidity at 40 °C.

The Reflex iC60N series sits within the broader Acti9 platform, meaning panel builders already standardised on Acti9 can drop this into an existing board without changing the upstream selectivity study or busbar arrangement.

Frequently asked questions

What breaking capacity does the A9C61225 have at 230 V AC?

20 kA Icu at 220–240 V AC per EN/IEC 60947-2, which drops to 10 kA at 380–415 V AC.

What control voltage options does this Reflex iC60N accept?

The control circuit accepts 230 V AC, 24 V AC, 48 V AC, 24 V DC, and 48 V DC — covering both mains-voltage and low-voltage control schemes.

How does the integrated control work on this MCB?

It accepts remote control by pulse, by continuous command, or via a toggle ON/OFF button on the front face, with local LED indication for device state, trip, fault, and overheat.