Skip to main content
Schneider Electric A9C61416 — Contactors

Schneider A9C61416 Reflex iC60N, 16 A 4P Curve B Integrated

MPNA9C61416
Obsolete

Schneider Electric Acti9 Reflex iC60N, integrated control circuit breaker, 16 A, 4P, curve B, 20 kA Icu at 240 V AC, 35 mm DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9C61416 — Identification
ParameterValue
Product / component typeIntegrated control circuit breaker
Series / rangeActi9
A9C61416 — Contacts & Poles
ParameterValue
Pole configuration4P
A9C61416 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
A9C61416 — Mechanical
ParameterValue
Width117 mm
Height84 mm
Depth77 mm

Product details

The Schneider Electric A9C61416 is a Reflex iC60N integrated control circuit breaker from the Acti9 range — a 4-pole, 16 A, curve B device that combines overcurrent protection with remote control capability in a single DIN-rail package. It is rated for 20 kA breaking capacity at 220–240 V AC and 10 kA at 380–415 V AC, per EN/IEC 60947-2, making it suitable for final distribution and control circuits in commercial and light industrial panels. The integrated control function accepts a maintained or pulsed control signal (230 V AC, 24 V AC, 48 V AC, 24 V DC, or 48 V DC) to remotely open or close the breaker, with local toggle and push-button override. A red/green LED provides status: green for ON, flashing red for fault, overheat, or trip, and steady flashing for device-ready.

The 4P body occupies 13 x 9 mm pitches — 117 mm wide — with a depth of 77 mm and height of 84 mm. IP20 rated per IEC 60529, so it belongs inside a panel, not exposed to washdown. Pollution degree 3 rated, meaning it handles conductive pollution typical of control cabinets.

Key ratings in context

Curve B trips magnetically at 3–5x In (48–80 A), so it is best for resistive or light inductive loads — not for high-inrush motor starts. Electrical durability is 50,000 cycles at AC-1 (resistive load); mechanical durability matches at 50,000 cycles. Earth-leakage protection requires a separate block — not built in. Padlockable in the OFF position (provision for padlocking) with a contact position indicator. Tropicalisation class 2 means it withstands 93% relative humidity at 40 °C without condensation issues.

Frequently asked questions

What is the breaking capacity of the A9C61416?

20 kA Icu at 220–240 V AC and 10 kA Icu at 380–415 V AC, both per EN/IEC 60947-2. Breaking capacity code is N.

What control voltages does the A9C61416 accept?

The control circuit accepts 230 V AC, 24 V AC, 48 V AC, 24 V DC, or 48 V DC — both maintained and pulsed signals.

What is the physical size of the A9C61416?

Width 117 mm (13 x 9 mm pitches), height 84 mm, depth 77 mm. Mounts on 35 mm symmetrical DIN rail.

MPN
A9C61416