Skip to main content
Schneider Electric A9C61463 — Contactors

Schneider Electric A9C61463 Reflex iC60N, 63 A 4P Curve B

MPNA9C61463
Active

Schneider Electric Acti9 Reflex iC60N, integrated control MCB, 63 A, 4P, curve B, 20 kA Icu at 240 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

A9C61463 — Identification
ParameterValue
Product / component typeIntegrated control circuit breaker
Series / rangeActi9
A9C61463 — Contacts & Poles
ParameterValue
Pole configuration4P
A9C61463 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
A9C61463 — Mechanical
ParameterValue
Width117 mm
Height84 mm
Depth77 mm

Product details

The Schneider Electric A9C61463 is an integrated control circuit breaker from the Acti9 Reflex iC60N range, combining overcurrent protection with remote switching capability in a single 4-pole unit rated at 63 A with a B tripping curve. It offers a breaking capacity of 20 kA Icu at 220...240 V AC and 10 kA Icu at 380...415 V AC, per EN/IEC 60947-2, which means it can safely interrupt fault currents up to those levels without upstream damage in a distribution panel. The control circuit accepts multiple signal types — 230 V AC, 24 V AC, 48 V AC, 24 V DC, and 48 V DC — and supports impulse, maintained, or maintained very low voltage commands via the toggle or remote control.

Where and how it mounts

Electrical durability of 50,000 cycles under AC-1 resistive load at 50 Hz, matching the mechanical durability — this is a switching device rated for frequent operation, not just backup protection. Earth-leakage protection requires a separate block (Vigi iC60), so if ground-fault protection is needed, order the add-on module — not integrated here.

Frequently asked questions

What is the breaking capacity of the A9C61463?

It has a breaking capacity of 20 kA Icu at 220...240 V AC and 10 kA Icu at 380...415 V AC, conforming to EN/IEC 60947-2.

What control voltages does the A9C61463 accept?

The control circuit accepts 230 V AC, 24 V AC, 48 V AC, 24 V DC, and 48 V DC, supporting impulse, maintained, or maintained very low voltage commands.

Does the A9C61463 include earth-leakage protection?

No, earth-leakage protection requires a separate Vigi iC60 block — it is not integrated into this unit.

What is the physical size and mounting of the A9C61463?

It measures 117 mm wide (13 module pitches), 84 mm high, and 77 mm deep, and mounts on a 35 mm symmetrical DIN rail.

MPN
A9C61463