Schneider Electric A9C63316 — Contactors

Schneider Electric A9C63316 Reflex iC60N Ti24 16 A 3P curve

MPNA9C63316
Obsolete

Schneider Electric Acti9 Reflex iC60N Ti24, 16 A, 3P, curve D, 20 kA Icu at 230 V AC, integrated control MCB.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9C63316 — Identification
ParameterValue
Product / component typeIntegrated control circuit breaker
Series / rangeActi9
A9C63316 — Contacts & Poles
ParameterValue
Pole configuration3P
A9C63316 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
A9C63316 — Mechanical
ParameterValue
Width99 mm
Height84 mm
Depth77 mm

Product details

The Schneider Electric A9C63316 is a Reflex iC60N Ti24 integrated control circuit breaker from the Acti9 range — a 3-pole, 16 A thermal-magnetic MCB with a D curve, designed for distribution and control applications on AC networks at 50/60 Hz. Breaking capacity is 20 kA Icu at 220…240 V AC and 10 kA Icu at 380…415 V AC, both per EN/IEC 60947-2 — enough for most industrial panel secondary distribution.

Control and integration

This isn't just a breaker — it's an integrated control device with an ON/OFF button and remote control capability via pulse or continuous command, using a separate control voltage (230 V AC, 24 V AC/DC, or 48 V AC/DC). Mounts on a 35 mm symmetrical DIN rail (fixed mounting), taking 11 × 9 mm pitches of panel space — 99 mm wide, 84 mm high, 77 mm deep. IP20 rated per IEC 60529, so it's for dry indoor enclosures only; pollution degree 3 suits industrial environments with conductive pollution.

Earth-leakage protection is handled by a separate block (not built in), so if you need RCD functionality, plan for an add-on Vigi module.

Frequently asked questions

What are the key ratings for this MCB?

16 A rated current, 3-pole, D curve, 20 kA Icu at 230 V AC (10 kA at 415 V AC) per EN/IEC 60947-2, with a 230 V AC control circuit voltage option.

What control voltages does it accept?

The control circuit accepts 230 V AC, 24 V AC/DC, and 48 V AC/DC — three options covering most panel control schemes.

Does it include earth-leakage protection?

No — earth-leakage protection requires a separate block (Vigi module); this is the thermal-magnetic MCB only.