Skip to main content
Schneider Electric A9C64310 — Contactors

Schneider Electric A9C64310 Reflex iC60H, 10 A, 3P, Curve B

MPNA9C64310
Obsolete

Schneider Electric Acti9 Reflex iC60H integrated control MCB, A9C64310, 10 A, 3P, curve B, thermal-magnetic trip, 30 kA breaking capacity.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9C64310 — Identification
ParameterValue
Product / component typeIntegrated control circuit breaker
Series / rangeActi9

Contacts & Poles

A9C64310 — Contacts & Poles
ParameterValue
Pole configuration3P

Environmental

A9C64310 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529

Mechanical

A9C64310 — Mechanical
ParameterValue
Width99 mm
Height84 mm
Depth77 mm

Product details

It combines overcurrent protection and remote switching in a single 3-pole device, rated at 10 A with a B curve for fast trip on short circuits.

Breaking capacity is 30 kA Icu at 220...240 V AC and 15 kA Icu at 380...415 V AC, per EN/IEC 60947-2.

Occupies 11 x 9 mm pitches (99 mm wide). Fixed mounting mode — no plug-in base. IP20 rated, so it belongs inside a panel, not exposed to washdown. Padlockable in the OFF position for lockout/tagout. Local signalling includes a green LED for device ON, red for fault, and flashing for overheat or tripped state.

Frequently asked questions

What are the control voltage options for the A9C64310?

The control circuit accepts 230 V AC, 24 V AC, 48 V AC, 24 V DC, or 48 V DC. The rated supply voltage is 230 V AC at 50/60 Hz.

What is the breaking capacity of the A9C64310?

30 kA Icu at 220...240 V AC and 15 kA Icu at 380...415 V AC, both per EN/IEC 60947-2.

What is the physical size of the A9C64310?

Height 84 mm, width 99 mm, depth 77 mm. Occupies 11 x 9 mm DIN-rail pitches.

MPN
A9C64310