Skip to main content
Schneider Electric A9C64316 — Contactors

Schneider Electric A9C64316 Reflex iC60H, 16 A 3P Curve B MC

MPNA9C64316
Obsolete

Schneider Electric Acti9 Reflex iC60H, integrated control circuit breaker, 16 A, 3P, curve B, 30 kA breaking capacity.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9C64316 — Identification
ParameterValue
Product / component typeIntegrated control circuit breaker
Series / rangeActi9

Contacts & Poles

A9C64316 — Contacts & Poles
ParameterValue
Pole configuration3P

Environmental

A9C64316 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529

Mechanical

A9C64316 — Mechanical
ParameterValue
Width99 mm
Height84 mm
Depth77 mm

Product details

The Schneider Electric A9C64316 is an integrated control circuit breaker from the Acti9 Reflex iC60H series — a thermal-magnetic MCB with a built-in remote control function, intended for distribution and control applications on 50/60 Hz AC networks. Rated at 16 A with a curve B trip characteristic, it protects against overload and short-circuit while providing local and remote switching via a maintained or impulse control signal at 230 V AC, 24 V AC, 48 V AC, 24 V DC, or 48 V DC.

The 30 kA Icu breaking capacity at 220…240 V AC (15 kA at 380…415 V) per EN/IEC 60947-2 means this breaker can safely interrupt fault currents up to that level without welding or rupturing — critical for high-fault-capacity installations where SCCR coordination upstream matters. Do not use for motor starting unless the inrush is verified below 5× rated current. The thermal-magnetic trip unit provides overload protection via a bimetal strip and short-circuit protection via a solenoid — no electronics to drift, qualifiable under change control for GMP environments.

Mounts on a standard 35 mm symmetrical DIN rail (EN 60715), occupies 11 x 9 mm pitches (99 mm width), and is IP20 finger-safe — suitable for enclosure installation where personnel access is restricted. The remote control function accepts both maintained and impulse commands, with local ON/OFF toggle and a padlockable OFF position for lockout/tagout. LED signalling indicates device state (on, tripped, fault, ready, overheat) — supports the audit trail during commissioning and troubleshooting. Earth-leakage protection is handled by a separate block (not integrated), so if RCD function is needed, plan for an adjacent Vigi module in the same enclosure.

For GMP validation, the manufacturer provides the standard documentation package (declaration of conformity, RoHS/REACH statements, UL file) under change control. Request the specific certificate for EN/IEC 60947-2 from your Schneider Electric contact to support IQ/OQ.

Frequently asked questions

What is the closest alternative to A9C64316 in this family?

No direct pin-compatible alternative exists within the Reflex iC60H series for this rating — the A9C64316 is the only variant combining 16 A, 3P, curve B, and 230 V AC control voltage. For a different curve (C or D) or rating, see the Reflex iC60H family table.

What is the depth of A9C64316?

The depth is 77 mm.

What range does A9C64316 belong to?

It belongs to the Acti9 range.

What compliance documentation is available for A9C64316?

The breaker is certified to EN/IEC 60947-2 for breaking capacity and carries IP20 per IEC 60529. The manufacturer typically provides RoHS, REACH, and UL declarations under change control — request the specific certificates from your Schneider Electric distributor.

MPN
A9C64316