Skip to main content
Schneider Electric A9C66416 — Contactors

Schneider Electric A9C66416 Reflex iC60H Ti24 16A 4P Curve D

MPNA9C66416
Active

Schneider Electric Acti9 Reflex iC60H Ti24, integrated control circuit breaker, 16 A, 4P, curve D, 230 V AC control, 30 kA breaking capacity.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9C66416 — Identification
ParameterValue
Product / component typeIntegrated control circuit breaker
Series / rangeActi9

Contacts & Poles

A9C66416 — Contacts & Poles
ParameterValue
Pole configuration4P

Environmental

A9C66416 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529

Mechanical

A9C66416 — Mechanical
ParameterValue
Width117 mm
Height84 mm
Depth77 mm

Product details

The Schneider Electric A9C66416 is a Reflex iC60H integrated control circuit breaker from the Acti9 range — a 4-pole thermal-magnetic MCB with a 16 A rated current and a D trip curve, designed to both protect and remotely control a circuit from a single DIN-rail footprint. Rated breaking capacity hits 30 kA Icu at 220…240 V AC and 15 kA Icu at 380…415 V AC, both per EN/IEC 60947-2, which means it can safely interrupt fault currents up to those levels without welding its contacts or cascading failure upstream. Control voltage options include 230 V AC, 24 V AC, 48 V AC, 24 V DC, and 48 V DC, so you can match whatever control signal your panel already runs — maintained, maintained very low voltage, or impulse commands.

Where you'd use it

This is an integrated control circuit breaker — it combines overcurrent protection (thermal-magnetic trip) with remote ON/OFF switching in one unit, so it's a natural fit for distribution and control panels where you want to shed a load or reset a circuit from a PLC or pushbutton without adding a separate contactor. The IP20 finger-safe terminals are fine for enclosed panels; the white housing and local LED signalling (green for ON, red for fault, flashing for ready/tripped/overheat) give a clear visual at the cabinet door.

Frequently asked questions

What are the key ratings for this Reflex iC60H?

16 A rated current, curve D trip characteristic, 4 poles protected, 30 kA breaking capacity at 230 V AC (15 kA at 415 V AC), control voltages available from 24 V DC up to 230 V AC.

What control signal types does it accept?

It accepts maintained signals (including very low voltage), impulse commands, and toggle remote control — so you can drive it from a latching relay, a momentary pushbutton, or a PLC digital output.

Does the A9C66416 include earth-leakage protection?

No, earth-leakage protection requires a separate block — this is the thermal-magnetic MCB only, not an RCBO. You'd add a Vigi iC60 module downstream if you need ground-fault detection.