Schneider Electric A9CR1225 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9CR1225 Acti9 RED RCCB, 25 A, 30 mA, 2P

MPNA9CR1225
Active

Schneider Electric Acti9 RED, RCCB, 2P, 25 A, 30 mA, Type A, 230 V AC, recloser, EN 50557.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9CR1225 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Local signalling / indication1 LED green/red Residual current device : ON/OFF indication Recloser : ON/OFF indication
A9CR1225 — Electrical Ratings
ParameterValue
Rated current (In)25 A
Rated operational voltage (Ue)230 V AC 50 Hz phase to neutral
Poles description2P
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)500 V
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemOutgoer
Mechanical durability (operating cycles)4000 cycles open-close
A9CR1225 — Identification
ParameterValue
Product nameActi9 RED
Product / component typeResidual current circuit breaker (RCCB)
Device short nameRED
A9CR1225 — Mechanical
ParameterValue
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Control typeToggle
Width in 9 mm modules6
Terminal connectionsGuard tunnel terminal 35 mm² rigid Guard tunnel terminal 35 mm² flexible Guard tunnel terminal 35 mm² flexible with ferrule
Wire stripping length12 mm
Terminal tightening torque3 N.m
Width54 mm
Height106 mm
Depth82 mm
A9CR1225 — Environmental
ParameterValue
Operating ambient temperature-5...40 °C
Storage ambient temperature-40...70 °C
IP degree of protectionIP20
Relative humidity95 % at 55 °C
Tropicalisation2
A9CR1225 — Approvals
ParameterValue
StandardsEN 50557

Product details

The recloser logic is the defining feature: after a fault trip, it waits 10 seconds, then attempts a reclose. If the insulation fault persists, it stops the restart cycle after three consecutive attempts, with a minimum 180-second interval between closings. This handles transient faults — a lightning strike or a momentary cable touch — without a site visit, but locks out on a hard fault.

The 25 A rating matches a 4 mm² copper feeder on a 230 V single-phase supply, typical for a lighting or general-purpose socket-outlet submain. The device is rated for 500 V insulation voltage (Ui) and complies with EN 50557, the standard for automatic reclosing devices for RCCBs. The 8/20 µs wave immunity rating of 250 A means it will not nuisance-trip on common surge events.

The fixed mounting mode and 54 mm width (9 mm pitch × 6) mean it occupies six modular spaces in a consumer unit or distribution board. Depth is 82 mm, height 106 mm — check enclosure depth before specifying, especially in shallow flush-mount boards. Tightening torque is 3 N·m; strip length 12 mm. The toggle control provides manual on/off and a test function that operates above 100 V.

Frequently asked questions

What is the A9CR1225's earth-leakage reset method?

It uses a fault reset for earth leakage — the device must be manually reset after a fault trip clears, unless the automatic recloser logic has cycled through its attempts.

What earthing systems is the A9CR1225 compatible with?

It is rated for TN-S and TT systems. The 2P switching and Type A sensitivity cover the fault-current paths in both configurations.

Where can I buy the A9CR1225?

The A9CR1225 is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at the time of quote.

MPN
A9CR1225