RCCB recloser with automatic restart logic
The recloser logic operates on a 10-second reclosing time, up to 30 cycles per hour, with a maximum of three consecutive restarts before locking out if the insulation fault persists. Minimum interval between two closings is 180 seconds.
Earthing system compatibility and installation
Occupies 6 x 9 mm pitches (54 mm wide). Depth is 82 mm, height 106 mm. Wire stripping length is 12 mm; tightening torque is 3 N·m.
Listed as current production (active lifecycle stage).
Protection and diagnostics
Manual test function operates above 100 V. Local signalling via a green/red LED indicates RCCB ON/OFF and recloser status. Insulation fault diagnosis stops if a fault is detected; the device restarts only after a transient fault clears. Rated insulation voltage (Ui) is 500 V. Mechanical durability is 4000 open-close cycles. IP20 rated — suitable for enclosed distribution boards only. Compliant with EN 50557 (requirements for automatic reclosing devices for RCCBs). Tropicalisation class 2; relative humidity tolerance 95 % at 55 °C.