It's rated 6 A with a B curve (magnetic trip 3 to 5 times In), breaking 10 kA Icn at 230...240 V AC 50 Hz per EN/IEC 61009-2-1, and integrates 30 mA earth-leakage protection.
Clip-on mounting to DIN rail (EN 50022), neutral on the left. The 9 mm phase-to-neutral pitch matches the Acti9 busbar system — no special adapters needed. Terminals accept 1 to 16 mm² rigid or 1 to 10 mm² flexible; strip 15 mm and torque to 2 Nm. IP20 on the body, IP40 inside a modular enclosure.