Skip to main content
Schneider Electric A9D10816 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9D10816 Acti9 iC60 RCBO, 16 A, 10 mA, 10

MPNA9D10816
Active

Schneider Electric Acti9 iC60 RCBO, 1P + N, 16 A, C-curve, 10 mA earth-leakage, 10 kA Icn at 230/240 V AC, clip-on DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9D10816 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)10 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage dependent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication
A9D10816 — Electrical Ratings
ParameterValue
Rated current (In)16 A at 50 °C
Rated operational voltage (Ue)230/240 V AC 50/60 Hz
Poles description1P + Ns
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)400 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemOutgoer
Electrical durability5000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D10816 — Identification
ParameterValue
Product nameActi9 iC60 RCBO
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiC60H RCBO
A9D10816 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules2
Terminal connectionsScrew clamp terminal (top) 1...25 mm² rigid without cable end Screw clamp terminal (top) 1...16 mm² flexible Screw clamp terminal (bottom) 1...16 mm² rigid without cable end Screw clamp terminal (bottom) 1...10 mm² flexible
Wire stripping lengthPower circuit: 13 mm for bottom connection Power circuit: 14 mm for top connection
Terminal tightening torquePower circuit: 3.5 N.m top Power circuit: 2 N.m bottom
Width18 mm
Height110 mm
Depth77.5 mm
A9D10816 — Environmental
ParameterValue
Operating ambient temperature-15...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
Relative humidity95 % at 55 °C
Tropicalisation2
A9D10816 — Approvals
ParameterValue
StandardsIEC 61009-2-2 IEC 61009-1 AS/NZS 61009.1 BS EN 61009-1

Product details

The Schneider Electric A9D10816 is an Acti9 iC60 RCBO — a combined residual-current circuit breaker with overcurrent protection in a single 18 mm wide module. The 10 kA breaking capacity at 230/240 V AC (Icn per IEC 61009-1) means it can safely interrupt a fault current up to that level without welding its contacts or cascading upstream — sized for residential and light commercial distribution boards where the prospective short-circuit current stays under that limit. The C-curve trips between 5 and 10 times rated current, so the 16 A unit holds through motor inrush and transformer energisation but clears a hard short fast. Thermal-magnetic trip technology gives a bimetal element for overload and a solenoid for short-circuit — no electronics to drift. Rated 16 A at 50 °C; if your enclosure runs hotter, derate per the manufacturer's thermal curve.

Integration notes

Tightening torque is 3.5 N·m on the top connection, 2 N·m on the bottom. Wire stripping length is 14 mm for the top, 13 mm for the bottom.

Frequently asked questions

Who supplies A9D10816 and how is it quoted?

The A9D10816 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the closest pin-compatible alternative to A9D10816?

Within the Acti9 iC60 RCBO family, the closest alternative would be a unit with the same pole configuration (1P + N), same C-curve, and same 10 mA leakage sensitivity but a different rated current — for example, a 10 A or 20 A variant. The mechanical footprint (18 mm width, clip-on DIN rail) is identical across the iC60H range, so swapping current ratings does not change the panel layout.

What compliance documentation does this brand provide for A9D10816?

The A9D10816 is certified to IEC 61009-1, IEC 61009-2-2, AS/NZS 61009.1, and BS EN 61009-1. These cover the RCBO standard for residual current and overcurrent protection. RoHS and REACH compliance documentation is typically available from the manufacturer's product page or through the distributor upon request.

MPN
A9D10816