It carries a 32 A rated current (at 50 °C), a 10 kA breaking capacity (Icn at 230/240 V AC), and a 10 mA earth-leakage sensitivity. The thermal-magnetic trip unit provides both overload and short-circuit protection on a single 18 mm wide DIN-rail module.
The 10 kA breaking capacity at 230/240 V AC (Icn per IEC 61009-1) sets the maximum fault current this RCBO can safely interrupt — adequate for most commercial and light industrial final circuits where the prospective short-circuit current stays under 10 kA. The 10 mA earth-leakage threshold is a high-sensitivity trip, typically specified for circuits supplying wet areas, medical equipment, or where additional personal protection is required. The 32 A rating suits socket-outlet circuits or fixed equipment up to that load.
Clip-on mounting to a standard 45 mm grid DIN rail (EN 60715). The 18 mm width (2× 9 mm pitches) occupies a single modular slot. Neutral is on the left; the toggle provides ON/OFF local indication. IP20 finger-safe protection for panel installation.
Certified to BS EN 61009-1, IEC 61009-1, IEC 61009-2-2, and AS/NZS 61009.1 — covering RCBO performance, EMC, and Australian/New Zealand deviations. The TN earthing system is specified; tropicalisation class 2 (95 % RH at 55 °C) suits humid environments. Limitation class 3 (energy limiting) reduces let-through energy under fault conditions.