Schneider Electric A9D10845 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9D10845 Acti9 iC60H RCBO, 45 A, 10 mA, C

MPNA9D10845
Obsolete

Schneider Electric Acti9 iC60H RCBO, 1P+N, 45 A at 50 °C, 10 mA earth-leakage sensitivity, curve C, 10 kA breaking capacity, clip-on DIN rail, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9D10845 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)10 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage dependent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication
A9D10845 — Electrical Ratings
ParameterValue
Rated current (In)45 A at 50 °C
Rated operational voltage (Ue)230/240 V AC 50/60 Hz
Poles description1P + Ns
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)400 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemOutgoer
Electrical durability5000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D10845 — Identification
ParameterValue
Product nameActi9 iC60 RCBO
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiC60H RCBO
A9D10845 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules2
Terminal connectionsScrew clamp terminal (top) 1...25 mm² rigid without cable end Screw clamp terminal (top) 1...16 mm² flexible Screw clamp terminal (bottom) 1...16 mm² rigid without cable end Screw clamp terminal (bottom) 1...10 mm² flexible
Wire stripping lengthPower circuit: 13 mm for bottom connection Power circuit: 14 mm for top connection
Terminal tightening torquePower circuit: 3.5 N.m top Power circuit: 2 N.m bottom
Width18 mm
Height110 mm
Depth77.5 mm
A9D10845 — Environmental
ParameterValue
Operating ambient temperature-15...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
Relative humidity95 % at 55 °C
Tropicalisation2
A9D10845 — Approvals
ParameterValue
StandardsIEC 61009-2-2 IEC 61009-1 BS EN 61009-1 AS/NZS 61009.1

Product details

The Schneider Electric A9D10845 is an Acti9 iC60H RCBO — a residual current breaker with overcurrent protection, combining a 45 A thermal-magnetic MCB (curve C) and a 10 mA earth-leakage detector in a single 18 mm wide module that clips onto a DIN rail. Rated 45 A at 50 °C, it handles the load current for a final subcircuit while the 10 mA sensitivity catches leakage to ground — the kind of spec you see on circuits supplying wet areas or equipment where personnel protection matters.

Clip-on mounting on a DIN rail, 18 mm wide (2 x 9 mm pitches), neutral on the left, with screw-clamp terminals accepting up to 25 mm² rigid on the top and 16 mm² on the bottom. Torque settings: 3.5 N.m on the top (line) connection, 2 N.m on the bottom (load). Strip length 14 mm top, 13 mm bottom.

Frequently asked questions

What is A9D10845's listed depth?

The A9D10845 has a depth of 77.5 mm.

What is A9D10845's listed range?

The A9D10845 belongs to the Acti9 range.

What compliance documentation does this brand provide for A9D10845?

The A9D10845 is certified to IEC 61009-2-2, IEC 61009-1, BS EN 61009-1, and AS/NZS 61009.1.

MPN
A9D10845