It combines a 40 A thermal-magnetic trip (curve C) with integrated 100 mA earth-leakage protection, all in a 1P + Ns (switched neutral) format. Clip-on mounting to DIN rail, with a 77.5 mm depth that fits standard distribution boards.
The 100 mA earth-leakage sensitivity is a common choice for general-purpose protection where 30 mA is not required; it reduces nuisance tripping on circuits with natural leakage.
The 18 mm width occupies two 9 mm pitches on a DIN rail — standard for a 1P + N RCBO. Clip-on mounting with a grid distance of 45 mm. Screw-clamp terminals accept up to 25 mm² rigid on top and 16 mm² flexible on bottom; tightening torque is 3.5 N.m top, 2 N.m bottom.