It occupies 2 x 9 mm pitches on a DIN rail, making it a compact choice for final subcircuit protection in TN earthing systems. Integrated earth-leakage protection at 100 mA sensitivity means this single device provides both overcurrent and residual current protection for a 1-pole circuit with switched neutral (1P + Ns).
The 10 kA Icn rating at 230/240 V AC is the device's rated short-circuit capacity per IEC 61009-1. For installations where the prospective fault current exceeds 10 kA, this unit would need upstream current-limiting protection — check your supply transformer impedance and cable run. If your load has a high inrush (transformer primary, large capacitor bank), a D-curve variant would be the better call. 100 mA earth-leakage sensitivity suits equipment protection or circuits where nuisance tripping from leakage is a concern.
Clip-on mounting to a standard DIN rail. Strip lengths are 14 mm (top) and 13 mm (bottom). IP20 finger protection — suitable for enclosed distribution boards only.