Skip to main content
Schneider Electric A9D14806 — Residual Current Breakers (RCCB/RCBO)

A9D14806 Acti9 iC60 RCBO, 6 A, 30 mA, C-Curve

MPNA9D14806
Active

Schneider Electric Acti9 iC60H RCBO, 1P+N, 6 A, 30 mA, C-curve, 10 kA, 240 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9D14806 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage dependent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication
A9D14806 — Electrical Ratings
ParameterValue
Rated current (In)6 A at 50 °C
Rated operational voltage (Ue)230/240 V AC 50/60 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)400 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemOutgoer
Electrical durability5000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D14806 — Identification
ParameterValue
Product nameActi9 iC60 RCBO
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiC60H RCBO
A9D14806 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules2
Terminal connectionsScrew clamp terminal (top) 1...25 mm² rigid without cable end Screw clamp terminal (top) 1...16 mm² flexible Screw clamp terminal (bottom) 1...16 mm² rigid without cable end Screw clamp terminal (bottom) 1...10 mm² flexible
Wire stripping lengthPower circuit: 13 mm for bottom connection Power circuit: 14 mm for top connection
Terminal tightening torquePower circuit: 3.5 N.m top Power circuit: 2 N.m bottom
Width18 mm
Height110 mm
Depth77.5 mm
A9D14806 — Environmental
ParameterValue
Operating ambient temperature-15...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Relative humidity95 % at 55 °C
Tropicalisation2
A9D14806 — Approvals
ParameterValue
StandardsIEC 61009-2-2 IEC 61009-1

Product details

The Schneider Electric A9D14806 is an Acti9 iC60H RCBO — a residual current breaker with overcurrent protection, combining a 6 A thermal-magnetic MCB and a 30 mA earth-leakage module in a single 18 mm wide, 1P+N package.

The A9D14806 clips onto a standard DIN rail (35 mm per EN 60715) and occupies 2 x 9 mm pitches (18 mm width). It is an outgoer device in a distribution board, with screw-clamp terminals accepting up to 25 mm² rigid cable on the top and 16 mm² on the bottom. The IP20 body is rated for modular enclosures (IP40). A padlock with Ø 4 mm shackle can lock the toggle in the OFF position for lockout/tagout.

The 6 A rated current (In) is specified at 50 °C ambient — no derating needed at typical panel temperatures up to that point. The 30 mA earth-leakage sensitivity provides additional protection against electric shock for final circuits.

Frequently asked questions

What is A9D14806's listed depth (77.5 mm) on this component line?

The A9D14806 has a depth of 77.5 mm, a width of 18 mm (2 x 9 mm pitches), and a height of 110 mm.

What compliance documentation does this brand provide for A9D14806 (RoHS, REACH, UL, IEC)?

The A9D14806 is certified to IEC 61009-1 and IEC 61009-2-2, which are the relevant product standards for RCBOs. It is designed for TN earthing systems and carries IP20/IP40 protection ratings per IEC 60529.

Where can I buy A9D14806 and what is the lead time?

The A9D14806 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or lead-time number is published here.

MPN