Schneider Electric A9D14810 — Residual Current Breakers (RCCB/RCBO)

A9D14810 Acti9 iC60H RCBO, 10 A, 30 mA, 10 kA

MPNA9D14810
Active

Schneider Electric Acti9 iC60H RCBO, 1P+N, 10 A rated current, 30 mA earth-leakage sensitivity, 10 kA breaking capacity, curve C, DIN-rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9D14810 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage dependent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication
A9D14810 — Electrical Ratings
ParameterValue
Rated current (In)10 A at 50 °C
Rated operational voltage (Ue)230/240 V AC 50/60 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)400 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemOutgoer
Electrical durability5000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D14810 — Identification
ParameterValue
Product nameActi9 iC60 RCBO
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiC60H RCBO
A9D14810 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules2
Terminal connectionsScrew clamp terminal (top) 1...25 mm² rigid without cable end Screw clamp terminal (top) 1...16 mm² flexible Screw clamp terminal (bottom) 1...16 mm² rigid without cable end Screw clamp terminal (bottom) 1...10 mm² flexible
Wire stripping lengthPower circuit: 13 mm for bottom connection Power circuit: 14 mm for top connection
Terminal tightening torquePower circuit: 3.5 N.m top Power circuit: 2 N.m bottom
Width18 mm
Height110 mm
Depth77.5 mm
A9D14810 — Environmental
ParameterValue
Operating ambient temperature-15...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Relative humidity95 % at 55 °C
Tropicalisation2
A9D14810 — Approvals
ParameterValue
StandardsIEC 61009-2-2 IEC 61009-1

Product details

The A9D14810 is a Schneider Electric Acti9 iC60H RCBO — a combined residual-current circuit breaker with overcurrent protection in a single 18 mm wide, 1P+N module. It carries a 10 A rated current at 50 °C, a 30 mA earth-leakage sensitivity, and a 10 kA breaking capacity (Icn at 240 V AC, per IEC 61009-1).

Clip-on mounting to a 45 mm grid DIN rail. The module takes two 9 mm pitches of rail space. Neutral is on the left. IP20 on the body, IP40 inside a modular enclosure — that's standard for a panelboard, not a washdown location.

Frequently asked questions

Where can I buy the A9D14810 and get a price?

The A9D14810 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the A9D14810's depth?

The A9D14810 has a depth of 77.5 mm.

What compliance documentation does this brand provide for the A9D14810?

The A9D14810 is certified to IEC 61009-1 and IEC 61009-2-2. The IP ratings (IP20/IP40) are per IEC 60529.