The A9D15832 is a Schneider Electric Acti9 iC60H RCBO — a residual current breaker with overcurrent protection in a 1P+N format, rated 32 A at 50 °C with a C trip curve and a 10 kA Icn breaking capacity at 240 V AC. The integrated earth-leakage protection is set at 100 mA sensitivity, making it suitable for TN earthing systems where both overcurrent and ground-fault protection are required in a single 18 mm wide module.
In a typical domestic or light commercial distribution board fed by a transformer with a low-impedance path, that covers the majority of downstream faults. The 100 mA earth-leakage sensitivity is a deliberate choice — it is not a 30 mA personal-protection level. This RCBO is intended for equipment or circuit protection where a higher leakage threshold is acceptable (e.g., fixed industrial machinery, lighting circuits, or sub-distribution), not for socket-outlet circuits where 30 mA is standard for shock protection. The thermal-magnetic trip unit handles the overcurrent side; the integrated residual-current module handles the ground-fault side, all in one 18 mm wide, clip-on DIN-rail package.
Integration and installation
The toggle provides local ON/OFF indication, and the unit is padlockable with a 4 mm padlock for lockout/tagout.