A9D15840 Acti9 iC60 RCBO, 40 A, 10 kA, 100 mA, C-curve

MPNA9D15840
Active

Schneider Electric Acti9 iC60 RCBO, A9D15840, 1P+N, 40 A, C-curve, 10 kA Icn, 100 mA earth-leakage, DIN rail mount, current production.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9D15840 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)100 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage dependent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication
A9D15840 — Electrical Ratings
ParameterValue
Rated current (In)40 A at 50 °C
Rated operational voltage (Ue)230/240 V AC 50/60 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)400 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemOutgoer
Electrical durability5000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D15840 — Identification
ParameterValue
Product nameActi9 iC60 RCBO
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiC60H RCBO
A9D15840 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules2
Terminal connectionsScrew clamp terminal (top) 1...25 mm² rigid without cable end Screw clamp terminal (top) 1...16 mm² flexible Screw clamp terminal (bottom) 1...16 mm² rigid without cable end Screw clamp terminal (bottom) 1...10 mm² flexible
Wire stripping lengthPower circuit: 13 mm for bottom connection Power circuit: 14 mm for top connection
Terminal tightening torquePower circuit: 3.5 N.m top Power circuit: 2 N.m bottom
Width18 mm
Height110 mm
Depth77.5 mm
A9D15840 — Environmental
ParameterValue
Operating ambient temperature-15...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Relative humidity95 % at 55 °C
Tropicalisation2
A9D15840 — Approvals
ParameterValue
StandardsIEC 61009-1 IEC 61009-2-2

Product details

What this RCBO does on the rail

This is a current-production part, so no last-time-buy scramble.

The 100 mA earth-leakage threshold is less sensitive than a 30 mA RCD — that's deliberate: it's for circuits where nuisance tripping from cable capacitance or equipment leakage would be a problem, like long runs or industrial kit with filtering. The 10 kA Icn means it's rated for the full fault current at the panel's main bus; no need to upsize the upstream breaker just to protect this device.

Clip-on DIN rail mount, 2 x 9 mm pitches wide (18 mm). Neutral is on the left, so plan your busbar order. Strip length 14 mm top, 13 mm bottom. IP20 on the terminals, IP40 in the modular enclosure — fine for a clean panel, not for washdown. Padlockable with a 4 mm shackle for lockout/tagout.

Frequently asked questions

Where can I buy A9D15840 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is A9D15840's depth?

The depth is 77.5 mm.

What compliance documentation does this brand provide for A9D15840?

The part complies with IEC 61009-1 and IEC 61009-2-2 standards.

MPN