Skip to main content
Schneider Electric A9D17213 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9D17213 Acti9 iC60 RCBO, 13 A, 30 mA, C-

MPNA9D17213
Active

Schneider Electric Acti9 iC60 RCBO, A9D17213, 2P, 13 A rated, 30 mA earth leakage, C-curve, 10 kA Icn, clip-on DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9D17213 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON, OFF, fault trip
A9D17213 — Electrical Ratings
ParameterValue
Rated current (In)13 A
Rated operational voltage (Ue)220...240 V AC 50 Hz
Poles description2P
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)500 V AC 50 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII conforming to IEC 60364
Device location in systemOutgoer
Electrical durability10000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D17213 — Identification
ParameterValue
Product nameActi9 iC60 RCBO
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiC60 RCBO
A9D17213 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsTunnel type terminal top or bottom 1...35 mm² rigid Tunnel type terminal top or bottom 1...25 mm² flexible Tunnel type terminal top or bottom 1...25 mm² flexible with ferrule
Wire stripping length12 mm for top or bottom connection
Terminal tightening torque2 N.m
Width36 mm
Height86 mm
Depth78 mm
A9D17213 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...70 °C
IP degree of protectionIP40 (distribution enclosure) conforming to IEC 60529 IP20 conforming to IEC 60529
Relative humidity95 % at 55 °C
Tropicalisation2
A9D17213 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 61009-2-1

Product details

The Schneider Electric A9D17213 is an Acti9 iC60 RCBO — a combined residual-current circuit breaker with overcurrent protection, in a 2-pole (2P) form factor. It integrates both thermal-magnetic overcurrent tripping and 30 mA earth-leakage detection into a single 36 mm wide module that clips onto a DIN rail. The 13 A rating and 30 mA leakage sensitivity make this a go-to for final subcircuits in distribution boards: socket outlets, small appliance circuits, or lighting final circuits where personnel protection against indirect contact is required.

Rated breaking capacity is 10 kA Icn at 220...240 V AC 50 Hz per EN/IEC 61009-2-1, with an ultimate breaking capacity (Icu) of 15 kA at the same voltage per EN/IEC 60947-2. The higher Icu figure gives headroom for coordination studies; if the upstream device limits the prospective fault current below 15 kA, this RCBO can handle the let-through without losing its integrity.

Clip-on mounting to DIN rail — standard 35 mm symmetrical rail. Connection pitch is 9 mm between poles, which aligns with the busbar system for the Acti9 range. The toggle provides local signalling: ON, OFF, and fault-trip positions are clearly indicated. IP40 in a distribution enclosure, IP20 otherwise — so it's not rated for washdown environments; keep it inside a panel.

Frequently asked questions

Where can I buy the A9D17213 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the breaking capacity of the A9D17213?

The A9D17213 has a rated breaking capacity (Icn) of 10 kA at 220...240 V AC 50 Hz per EN/IEC 61009-2-1, and an ultimate breaking capacity (Icu) of 15 kA at the same voltage per EN/IEC 60947-2.

What compliance documentation does Schneider provide for the A9D17213?

The A9D17213 carries KEMA-KEUR, VDE, NF, and IMQ quality labels. It is certified to EN/IEC 60947-2 and EN/IEC 61009-2-1 standards. RoHS and REACH compliance documentation is standard for the Acti9 range; request it with your RFQ.

MPN
A9D17213