The A9D17313 is a 3-pole RCBO from the Acti9 iC60 range, combining thermal-magnetic overcurrent protection (13 A rated, C-curve) with integrated 30 mA earth-leakage protection in a single DIN-rail module. It clips onto the rail and occupies 6 x 9 mm pitches (54 mm wide), fitting standard distribution boards. The breaking capacity is 10 kA Icn per EN/IEC 61009-2-1 at 220–240 V AC, 50 Hz, with an ultimate breaking capacity (Icu) of 15 kA per EN/IEC 60947-2.
The 30 mA earth-leakage sensitivity provides personal protection against indirect contact (touch voltage) per IEC 60364. The IP40 face (in enclosure) and IP20 terminals suit clean, dry panel environments; not rated for washdown.
Local signalling (ON, OFF, fault trip) visible through the white toggle. Tropicalisation class 2 for humid environments up to 95 % RH at 55 °C.