Skip to main content
Schneider Electric A9D27210 — Residual Current Breakers (RCCB/RCBO)

A9D27210 Acti9 iC60 RCBO, 10A, 30mA, C-curve, 2P

MPNA9D27210
Active

Schneider Electric Acti9 iC60 RCBO, A9D27210, 2P, 10 A rated, 30 mA earth leakage, C-curve, 10 kA breaking capacity, clip-on DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9D27210 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A-SI (Super Immunised)
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON, OFF, fault trip
A9D27210 — Electrical Ratings
ParameterValue
Rated current (In)10 A
Rated operational voltage (Ue)220...240 V AC 50 Hz
Poles description2P
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)500 V AC 50 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII conforming to IEC 60364
Device location in systemOutgoer
Electrical durability10000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D27210 — Identification
ParameterValue
Product nameActi9 iC60 RCBO
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiC60 RCBO
A9D27210 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsTunnel type terminal top or bottom 1...35 mm² rigid Tunnel type terminal top or bottom 1...25 mm² flexible Tunnel type terminal top or bottom 1...25 mm² flexible with ferrule
Wire stripping length12 mm for top or bottom connection
Terminal tightening torque2 N.m
Width36 mm
Height86 mm
Depth78 mm
A9D27210 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...70 °C
IP degree of protectionIP40 (distribution enclosure) conforming to IEC 60529 IP20 conforming to IEC 60529
Relative humidity95 % at 55 °C
Tropicalisation2
A9D27210 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 61009-2-1

Product details

The A9D27210 is a Schneider Electric Acti9 iC60 RCBO — a combined residual-current circuit breaker with overcurrent protection in a 2-pole, 36 mm wide package that clips onto DIN rail. It protects a single-phase outgoing circuit against overloads, short-circuits, and earth faults, all in one unit. The integrated earth-leakage protection trips at 30 mA — the standard sensitivity for personal shock protection in residential and commercial distribution boards. Breaking capacity is 10 kA Icn (service) and 15 kA Icu (ultimate) at 220...240 V AC, 50 Hz, per EN/IEC 61009-2-1 and EN/IEC 60947-2.

For BOM-freeze planning: the Acti9 iC60 series is Schneider's mainstream RCBO line, widely specified across Europe and Asia. No imminent replacement or form-factor change is signaled. If you need a compliance documentation package (CE, NF, VDE, KEMA-KEUR, IMQ), those marks are listed on the part itself.

Mounts on DIN rail via the clip-on mechanism — 4 pitches of 9 mm (36 mm total width). IP40 in a distribution enclosure, IP20 for the terminal area — standard for panel-mount gear. The toggle gives local ON/OFF/fault-trip indication. Tropicalisation class 2 means it handles 95 % RH at 55 °C without derating.

Frequently asked questions

What is the breaking capacity of A9D27210?

The A9D27210 has a service breaking capacity (Icn) of 10 kA and an ultimate breaking capacity (Icu) of 15 kA at 220...240 V AC, 50 Hz, per EN/IEC 61009-2-1 and EN/IEC 60947-2.

Where can I buy A9D27210 and how is it quoted?

The A9D27210 is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — no stock figures or prices are published here.

What compliance documentation does Schneider provide for A9D27210?

The A9D27210 carries quality labels NF, VDE, KEMA-KEUR, and IMQ, and complies with EN/IEC 60947-2 and EN/IEC 61009-2-1 standards. Standard CE declaration and product-specific compliance docs are available on request.

MPN
A9D27210