Rated 13 A with a B-curve magnetic trip (3 to 5 x In) and 30 mA earth-leakage sensitivity, it fits distribution sub-circuits where both fault types must be cleared in one unit.
Breaking capacity is 10 kA Icn at 230 V AC per EN/IEC 61009-2-1, with an ultimate capacity (Icu) of 15 kA at the same voltage per EN/IEC 60947-2. The 10 kA Icn covers the vast majority of commercial and light-industrial panel fault levels; the higher Icu gives margin for coordination studies where the upstream device limits let-through energy. The 30 mA earth-leakage threshold provides additional protection against indirect contact and fire risk from leakage to earth. Integrated into the RCBO package, it eliminates a separate RCD module and saves one DIN module of width — the unit occupies 4 pitches of 9 mm (36 mm total). This is relevant when coordinating with sensitive electronics or long cable runs.
Tunnel-type terminals accept 1 to 35 mm² rigid or 1 to 25 mm² flexible conductors; strip length is 12 mm and tightening torque is 2 N·m. IP40 faceplate rating in a distribution enclosure (IP20 for the terminals) suits indoor panel environments. The white housing with toggle control provides local ON/OFF and fault-trip indication.
Rated for 10,000 electrical cycles and 20,000 mechanical cycles — sufficient for typical branch-circuit duty in commercial and light-industrial panels.