Skip to main content
Schneider Electric A9D40616 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9D40616 Acti9 RCBO, 16 A, 10 mA, C-Curve

MPNA9D40616
Active

Schneider Electric Acti9 ISPN Vigi RCBO, 1P+N, 16 A, C-curve, 10 mA earth leakage, 6 kA breaking capacity, DIN rail clip-on, white.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9D40616 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)10 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage dependent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication
A9D40616 — Electrical Ratings
ParameterValue
Rated current (In)16 A at 30 °C
Rated operational voltage (Ue)230/240 V AC 50 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)400 V AC 50 Hz
Rated impulse withstand voltage (Uimp)4 kV
Electrical durability10000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D40616 — Identification
ParameterValue
Product nameISPN Vigi
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
A9D40616 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules2
Terminal connectionsTunnel type terminal (upstream) 1...16 mm² rigid Tunnel type terminal (downstream) 1...10 mm² rigid Tunnel type terminal (upstream) 1...16 mm² flexible Tunnel type terminal (downstream) 1...10 mm² flexible
Wire stripping length11 mm for downstream connection 13 mm for upstream connection
Terminal tightening torque2 N.m upstream 2 N.m downstream
Width18 mm
Height93 mm
Depth70 mm
A9D40616 — Environmental
ParameterValue
Operating ambient temperature-25...55 °C
Storage ambient temperature-25...70 °C
IP degree of protectionIP20
Relative humidity95 % at 55 °C
Tropicalisation2
A9D40616 — Approvals
ParameterValue
StandardsAS/NZS 61009.1 IEC 61009-2-2

Product details

It combines a 16 A thermal-magnetic circuit breaker (C-curve, magnetic trip 5–10 × In) with integrated 10 mA earth-leakage protection in a single 18 mm wide DIN-rail module. The C-curve suits inductive loads like small motors, pumps, and lighting banks where inrush is moderate.

Clip-on mounting to DIN rail, 2 module pitches (18 mm wide). Tightening torque 2 N·m both sides. Wire strip length 13 mm upstream, 11 mm downstream. Neutral on the left, ON/OFF toggle with positive contact position indicator.

Lifecycle stage is current production.

Frequently asked questions

How do I get current pricing and availability for A9D40616?

Submit an RFQ — the part is sourced to order through independent distribution, and availability with current pricing is confirmed at quote time.

What is A9D40616's rated current and earth leakage sensitivity?

Rated current is 16 A at 30 °C, with integrated 10 mA earth-leakage protection.

What compliance documentation does this brand provide for A9D40616?

The RCBO is certified to AS/NZS 61009.1 and IEC 61009-2-2. Standard documentation includes the manufacturer's declaration of conformity for those standards.

MPN
A9D40616