Rated 32 A at 30 °C with a C-curve magnetic trip (5...10 x In), it breaks 6000 A Icn at 230/240 V AC 50 Hz. The 10 mA sensitivity is the key spec here: that's the level used for personal shock protection in wet or exposed circuits (bathrooms, construction-site sockets, medical locations), not just equipment protection.
Clip-on mounting to a standard DIN rail, 2 x 9 mm pitches wide (18 mm). Depth is 70 mm, height 93 mm. That 18 mm width is the critical dimension for a crowded enclosure — it occupies exactly one standard modular position, so you can plan the rail fill without surprises. Wire stripping length is 13 mm upstream, 11 mm downstream. Tightening torque 2 N.m both sides.
Certified to AS/NZS 61009.1 and IEC 61009-2-2, the dual standard for RCBOs covering both overcurrent and residual-current protection in a single device. Suitability for isolation is marked, and the toggle provides ON/OFF indication with locking facilities.